D6: field forcing, D6-03: field forcing selection, D6-06: field forcing limit – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 177: 4 d: reference settings, Enables or disables the field forcing function

5.4 d: Reference Settings
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
177
P
a
ra
me
te
r De
ta
ils
5
◆ d6: Field Forcing
Field Forcing
The Field Forcing function compensates the delaying influence of the motor time constant when changing the excitation
current reference. Field Forcing can improve the motor responsiveness. It is ineffective during DC Injection Braking.
■
d6-03: Field Forcing Selection
Enables or disables the Field Forcing function.
Setting 0: Disabled
Setting 1: Enabled
■
d6-06: Field Forcing Limit
Sets the maximum level at which the Field Forcing function can boost the excitation current reference. The value is set as
a percentage of the motor no load current. This parameter does not normally need to be changed.
No.
Parameter Name
Setting Range
Default
d6-03
Field Forcing Selection
0 or 1
0
No.
Parameter Name
Setting Range
Default
d6-06
Field Forcing Limit
100 to 400%
400%