8.4 Option Card Installation

340

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

3.

Connect one end of the ground wire (H) to the ground terminal (I) using one of the remaining screws (C). Connect
the other end of the ground wire (H) to the remaining ground terminal and installation hole on the option (B) using
the last remaining provided screw (C).

Figure 8.5

Figure 8.5 Connect the Ground Wire

Note: 1. The option package includes two ground wires. Use the longer wire when plugging the option into connector CN5-C on the drive side.

Use the shorter wire when plugging the option into connector CN5-B. Refer to the option card instruction manual for more
information.

2. There are two screw holes on the drive for use as ground terminals (I). When connecting three options, two ground wires will need to

share the same drive ground terminal.

4.

Prepare and connect the wire ends as shown in

Figure 8.6

and

Figure 8.7

.

Refer to Wire Gauges, Tightening

Torque, and Crimp Terminals on page 345

to confirm that the proper tightening torque is applied to each

terminal. Take particular precaution to ensure that each wire is properly connected and wire insulation is not
accidentally pinched into electrical terminals.

WARNING! Fire Hazard. Tighten all terminal screws according to the specified tightening torque. Loose electrical connections could

result in death or serious injury by fire due to overheating electrical connections. Tightening screws beyond the specified tightening

torque may result in erroneous operation, damage to the terminal block, or cause a fire.

NOTICE: Heat shrink tubing or electrical tape may be required to ensure that cable shielding does not contact other wiring. Insufficient

insulation may cause a short circuit and damage the option or drive.

Figure 8.6

Figure 8.6 Preparing Ends of Shielded Cable

Figure 8.7

Figure 8.7 Preparing and Connecting Cable Wiring

I

B

H

C

YEA_com

Insulation

Shield sheath

Shield

PG option terminal

PG at motor

FE/SD

Ground Terminal

(Insulate with electrical tape
or shrink tubing)

B

3

Option terminal block

Preparing wire ends:

Screwdriver blade size

about 5.5 mm (7/32”)
When not using
crimped insulated
sleeves

Pull back the shielding and lightly
twist the end with fingers, keeping
the ends from fraying.

Shielded cable

(do not solder ends)

Loosen the screws and
insert the wire into the
opening on the terminal block.

Blade depth of
0.4 mm or less

Blade width of
2.5 mm or less