H: multi-function terminals, H1: multi-function digital inputs, B.3 parameter table – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 382

B.3 Parameter Table
382
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
◆ H: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
■
H1: Multi-Function Digital Inputs
F6-36
(3D1H)
CANopen Communication Speed
0: Auto-detection
1: 10 kbps
2: 20 kbps
3: 50 kbps
4: 125 kbps
5: 250 kbps
6: 500 kbps
7: 800 kbps
8: 1 Mbps
Default: 6
Min: 0
Max: 8
–
<1> Parameter setting value is not reset to the default value when the drive is initialized.
No.(Addr.)
Name
Description
Setting
Page
H1-03
(400H)
<19> With the speed reference priority d1-18 is set to 0 or 3, the default settings for parameters H1-03 to H1-07 governing input terminals S3 to S7
are: 24, 14, 3, 4, and 5 respectively. When d1-18 is set to 1 or 2, the default settings for H1-03 to H1-07 become 50, 54, 51, 53, and F
respectively.
Terminal S3 Function Selection
Assigns a function to the multi-function digital inputs.
Refer to page
for a description of setting values.
Note: Unused terminals should be set to F.
Default:
Min: 3
Max: 79
H1-04
(401H)
Terminal S4 Function Selection
Default:
Min: 3
Max: 79
H1-05
(402H)
Terminal S5 Function Selection
Default:
Min: 3
Max: 79
H1-06
(403H)
Terminal S6 Function Selection
Default:
Min: 3
Max: 79
H1-07
(404H)
Terminal S7 Function Selection
Default:
Min: 3
Max: 79
H1-08
(405H)
Terminal S8 Function Selection
Default: F
Min: 3
Max: 79
H1 Multi-Function Digital Input Settings
H1-
Setting
Function
Description
Page
3
Multi-Step Speed Reference 1
When input terminals are set to Multi-Step Speed References 1 through 3, switching combinations of those
terminals will create a multi-step speed sequence using the speed references set in d1-01 through d1-08.
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog reference selection
Closed: Jog frequency reference (d1-17) selected.
The Jog frequency can be used when the speed reference selection is not assigned to input terminals (b1-01
≠ 1)
and the speed reference priority is set to use the multi-step speed reference (d1-18 = 0 or 3).
7
Accel/decel Ramp Selection 1
Used to switch between accel/decel ramp 1 (set in C1-01, C1-02) and accel/decel ramp 2 (set in C1-03, C1-04).
When combined with another input terminal set for "Accel/Decel ramp 2" (H1- = 1A), the drive can also
switch between accel/decel ramp 3 (set in C1-05, C1-06) and accel/decel ramp 4 (set in C1-07, C1-08).
8
Baseblock Command (N.O.)
Closed: No drive output
9
Baseblock Command (N.C.)
Open: No drive output
F
Not Used (Through Mode)
Select this setting when the terminal is not used or when using the terminal in the pass-through mode. The terminal
does not trigger a drive function but can be used as digital input for the controller the drive is connected to.
No.(Addr.)
Name
Description
Setting
Page
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_
All Modes
common
_