D

L1-02: Motor Overload Protection Time

Setting Range: 0.1 to 5.0 min

Factory Default: 1.0 min

Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is
running at 60 Hz and at 150% of the full load amp rating (E2-01/E5-03) of the motor. Adjusting the value of L1-02 can
shift the set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.

Figure D.2

Figure D.2 Protection Operation Time for General Purpose Motors at the Rated Output Frequency

Operation time (minutes)

Cold start
(Characteristics when an overload occurs
at a complete stop)

Hot start
(Characteristics when an overload occurs
during continuous operation at 100%)

Motor current (%)

E2-01 = 100% motor current

10

7

3

1

0.4

0.1

0

100

150

200