L1-02: motor overload protection time, D.2 ul standards – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual
Page 457

D.2 UL Standards
YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual
457
St
an
dar
d
s
Complianc
e
D
■
L1-02: Motor Overload Protection Time
Setting Range: 0.1 to 5.0 min
Factory Default: 1.0 min
Parameter L1-02 determines how long the motor is allowed to operate before the oL1 fault occurs when the drive is
running at 60 Hz and at 150% of the full load amp rating (E2-01/E5-03) of the motor. Adjusting the value of L1-02 can
shift the set of oL1 curves up the y axis of the diagram below, but will not change the shape of the curves.
Figure D.2
Figure D.2 Protection Operation Time for General Purpose Motors at the Rated Output Frequency
Operation time (minutes)
Cold start
(Characteristics when an overload occurs
at a complete stop)
Hot start
(Characteristics when an overload occurs
during continuous operation at 100%)
Motor current (%)
E2-01 = 100% motor current
10
7
3
1
0.4
0.1
0
100
150
200