5.11 S: Elevator Parameters

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

257

P

a

ra

me

te

r De

ta

ils

5

Figure 5.48

Figure 5.48 Speed During Normal Operation

Advance Short Floor

Advanced Short Floor minimizes the operation time to arrive at a designated floor. It uses the leveling speed once the
leveling speed command is entered via one of the multi-function inputs (H1-†† = 53). Advance Short Floor calculates
optimal speed based on the Short Floor Minimum Constant Speed Time (S5-03) and the currently selected deceleration
rate.

Table 5.14

explains the Short Floor and Advance Short Floor functions.

Table 5.14 Short Floor Operation Example

Leveling Speed

Input Timing

Short Floor

Advanced Short Floor

Constant speed

operation at

rated speed

(normal stop

sequence)

During

acceleration

S

Speed

d1-19 (nominal speed)

d1-26 (leveling speed)

nominal speed

× 0.4

0

t

H1-

= 53

(Leveling Speed)

0

Operating
speed

Time

d1-19
(Nominal Speed)

d1-26
(Leveling Speed)

ON

(close)

(The speed is 40% of the nominal speed or more.)

d1-19
(Nominal Speed)

d1-26
(Leveling Speed)

H1-

= 53

(Leveling Speed

)

0

Operating
speed

Time

40% of nominal
speed

ON(close)

(The speed is over Optimum Speed.)

d1-19
(Nominal Speed)

Optimal Speed

d1-26
(Leveling Speed)

H1-

= 53

(Leveling Speed)

Operating
speed

0

ON

(close)

Time

(The speed is less than 40% of the nominal speed.)

H1-

= 53

(Leveling Speed)

d1-19
(Nominal Speed)

d1-26
(Leveling Speed)

40% of nominal
speed

ON(close)

0

Operating
speed

Time

(The speed is optimal speed or less.)

d1-19
(Nominal Speed)

Optimal Speed

d1-26
(Leveling Speed)

S5-03

H1-

= 53

(Leveling Speed

)

0

Operating
speed

ON

(close)

Time