YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

6.8 Diagnosing and Resetting Faults

6.8 Diagnosing and Resetting Faults

When a fault occurs and the drive stops, follow the instructions below to remove whatever conditions triggered the fault,
then restart the drive.

Fault Occurs Simultaneously with Power Loss

WARNING! Electrical Shock Hazard. Ensure there are no short circuits between the main circuit terminals (R/L1, S/L2, and T/L3) or

between the ground and main circuit terminals before restarting the drive. Failure to comply may result in serious injury or death and

will cause damage to equipment.

1.

Turn on the drive input power.

2.

Use monitor parameters U2-†† to display data on the operating status of the drive just before the fault occurred.

3.

Remove the cause of the fault and reset.

Note: 1. To find out what faults were triggered, check the fault history in U2-02. Information on drive status when the fault occurred such as

the output speed, current, and voltage can be found in U2-03 through U2-20.

Refer to Viewing Fault Trace Data After Fault on

page 304

for information on how to view fault data.

2. When the fault continues to be displayed after cycling power, remove the cause of the fault and reset.

If the Drive Still has Power After a Fault Occurs

1.

Look at the digital operator for information on the fault that occurred.

2.

Refer to Fault Displays, Causes, and Possible Solutions on page 276

3.

Reset the fault.

Refer to Fault Reset Methods on page 305

.

Viewing Fault Trace Data After Fault

Step

Display/Result

1.

Turn on the drive input power. The first screen displays.

2.

Press

or

until the monitor screen is displayed.

3.

Press

to display the parameter setting screen.

4.

Press

and

to scroll to monitor U2-02. The fault code shown in U2-02 is the fault that occurred last.

7.

Press

to view drive status information when fault occurred.

Parameters U2-03 through U2-20 help determine the cause of a fault.
Parameters to be monitored differ depending on the control mode.

- MODE -

U1-01= 0.00%

U1-02= 0.00%
U1-03= 0.00A

DRV

Speed Ref (OPR)

Rdy

RSEQ
LREF

FWD

- MODE -

U1-01= 0.00%

U1-02= 0.00%
U1-03= 0.00A

DRV

Monitor Menu

Rdy

FWD

RSEQ
LREF

-MONITR-

U

1

-01= 0.00%

U1-02= 0.00%
U1-03= 0.00A

DRV

Monitor

FWD

Rdy

RSEQ
LREF

FWD

- MONITR -

U2-

02

= oC

U2-03= 0.00%
U2-04= 0.00%

DRV

Last Fault

Rdy

RSEQ
LREF

FWD

FWD

- MONITR -

U2-

03

= 0.00%

U2-04= 0.00%
U2-05= 0.00A

DRV

Frequency Ref

Rdy

RSEQ
LREF

- MONITR -

U2-20= XX

°C

U2-01= -----
U2-02= -----

DRV

Heatsink Temp

Rdy

RSEQ
LREF