B.3 Parameter Table

390

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

L4: Speed Detection

L5: Automatic Fault Reset

L6: Torque Detection

<16> The setting value is dependent on the setting for the carrier frequency reduction (L8-38).

No. (Addr.)

Name

Description

Setting

Page

L4-01

(499H)

Speed Agreement Detection Level

L4-01 sets the speed detection level for digital output functions H2-†† = 3, 4, 5.
L4-02 sets the hysteresis or allowable margin for speed detection.

Default: 0.0%

Min: 0.0%
Max: 100.0%

219

L4-02

(49AH)

Speed Agreement Detection Width

Default: 4.0%

Min: 0.0%
Max: 40.0%

L4-03

(49BH)

Speed Agreement Detection Level
(+/-)

L4-03 sets the speed detection level for digital output functions H2-†† = 13, 14, 15, 16.
L4-04 sets the hysteresis or allowable margin for speed detection.

Default: 0.0%

Min: –100.0%
Max: 100.0%

220

L4-04

(49CH)

Speed Agreement Detection Width
(+/-)

Default: 4.0%

Min: 0.0%
Max: 40.0%

L4-05

(49DH)

Speed Reference Loss Detection
Selection

0: Stop. Drive stops when the speed reference is lost.
1: Run. Drive runs at a reduced speed when the speed reference is lost.

Default: 0

Min: 0
Max: 1

220

L4-06

(4C2H)

Speed Reference at Reference Loss Sets the percentage of the speed reference that the drive should run with when the speed

reference is lost.

Default: 80%

Min: 0.0%
Max: 100.0%

220

L4-07

(470H)

Speed Agree Detection Selection

0: No detection during baseblock
1: Detection always enabled

Default: 0

Min: 0
Max: 1

220

L4-13

(4F6H)

Door Zone Level

Sets the door zone speed level. The "door zone" multi-function digital output is closed when the
speed falls below this level.

Default: 0.0%

Min: 0.0%
Max: 100.0%

221

No. (Addr.)

Name

Description

Setting

Page

L5-01

(49EH)

Number of Auto Reset Attempts

Sets the number of times the drive may attempt to reset after the following faults occur: GF, LF,
oC, ov, rr, oH1, oL1, oL2, oL3, oL4, UL3, UL4.

Default: 0

Min: 0
Max: 10

222

L5-02

(49FH)

Fault Output Operation during
Auto Reset

0: Fault output not active.
1: Fault output active during reset attempt.

Default: 0

Min: 0
Max: 1

222

L5-06

(522H)

Undervoltage Fault Reset
Selection

0: Same as L5-01 condition
1: Always automatically reset UV1

Default: 0

Min: 0
Max: 1

222

No. (Addr.)

Name

Description

Setting

Page

L6-01

(4A1H)

Torque Detection Selection 1

0: Disabled
1: oL3 detection only active during speed agree, operation continues after detection
2: oL3 detection always active during run, operation continues after detection
3: oL3 detection only active during speed agree, output shuts down on an oL3 fault
4: oL3 detection always active during run, output shuts down on an oL3 fault
5: UL3 detection only active during speed agree, operation continues after detection
6: UL3 detection always active during run, operation continues after detection
7: UL3 detection only active during speed agree, output shuts down on an oL3 fault
8: UL3 detection always active during run, output shuts down on an oL3 fault

Default: 0

Min: 0
Max: 8

223

L6-02

(4A2H)

Torque Detection Level 1

Sets the overtorque and undertorque detection level.

Default: 150%

Min: 0%
Max: 300%

224

L6-03

(4A3H)

Torque Detection Time 1

Sets the time an overtorque or undertorque condition must exist to trigger torque detection 1.

Default: 0.1 s

Min: 0.0 s
Max: 10.0 s

224

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_