C.8 Message Examples

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

429

MEMOBUS

/Mo

dbu

s

C

o

m

m

u

ni

ca

ti

on

s

C

C.8 Message Examples

Below are some examples of command and response messages.

Reading Drive MEMOBUS/Modbus Register Contents

Using the function code 03H (Read), a maximum of 16 MEMOBUS/Modbus registers can be read out at a time.

The following table shows message examples when reading status signals, error details, data link status, and speed
references from the slave 2 drive.

Loopback Test

Function code 08H performs a loopback test. This test returns a response message with exactly the same content as the
command message and can be used to check communications between the master and slave. User-defined test code and
data values can be set.

The following table shows a message example when performing a loopback test with the slave 1 drive.

Command Message

Response Message (normal)

Response Message (fault)

Slave Address

02H

Slave Address

02H

Slave Address

02H

Function Code

03H

Function Code

03H

Function Code

83H

Starting No.

Upper

00H

Data Quantity

08H

Error Code

03H

Lower

20H

1st storage register

Upper

00H

CRC-16

Upper

F1H

Data Quantity

Upper

00H

Lower

65H

Lower

31H

Lower

04H

Next storage
register

Upper

00H

CRC-16

Upper

45H

Lower

00H

Lower

F0H

Next storage
register

Upper

00H

Lower

00H

Next storage
register

Upper

01H

Lower

F4H

CRC-16

Upper

AFH

Lower

82H

Command Message

Response Message (normal)

Response Message (fault)

Slave Address

01H

Slave Address

01H

Slave Address

01H

Function Code

08H

Function Code

08H

Function Code

88H

Test Code

Upper

00H

Test Code

Upper

00H

Error Code

01H

Lower

00H

Lower

00H

CRC-16

Upper

86H

Data

Upper

A5H

Data

Upper

A5H

Lower

50H

Lower

37H

Lower

37H

CRC-16

Upper

DAH

CRC-16

Upper

DAH

Lower

8DH

Lower

8DH

Advertising