C2: jerk settings, C1-10: accel/decel setting resolution, C1-15: inspection deceleration ramp – Yaskawa L1000E AC Drive Technical Manual for CIMR-LE Models for Elevator Applications User Manual

Page 164: 3 c: tuning

Advertising
background image

5.3 C: Tuning

164

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

NOTICE: Rapid deceleration can trigger an overvoltage fault. The drive output shuts off when faulted and the motor coasts. Set an

appropriate Fast Stop time to C1-09 to avoid this uncontrolled motor state and to ensure that the motor stops quickly and safely.

C1-10: Accel/Decel Setting Resolution

Determines the units for the acceleration and deceleration ramps set to C1-01 through C1-09 using parameter C1-10.

Setting 0: Two decimal places
Setting 1: One decimal place

C1-12/C1-13: Motor 2 Acceleration Time/Motor 2 Deceleration Time

Sets the accel/decel time when motor 2 has been selected using one of the multi-function input terminals (H1-

††

=16).

C1-15: Inspection Deceleration Ramp

Sets the deceleration ramp during Inspection Run. Refer to

Inspection Operation on page 124

for details.

C2: Jerk Settings

Jerk settings set the transition between acceleration rates. Adjust them to smooth out jerks or shocks that occur when the
speed is changed.

C2-01 to C2-05: Jerk Settings

C2-01 through C2-05 set separate jerks for each section of the acceleration or deceleration.

No.

<1> The setting range and default value depend on the display units set in parameter o1-03. If o1-03 is set between 0 and 4, the time required to go

from 0% speed to 100% maximum speed is expressed in seconds. If o1-03 is set to 5 or 6, then setting units will appear in m/s

2

or ft/s

2

. If the

drive is in V/f control mode, the Fast stop ramp can be set in seconds only.

Parameter Name

Setting Range

Default

C1-09

Fast Stop Ramp

0.0 to 600.0 s

<1>

1.50 s

<1>

No.

Parameter Name

Setting Range

Default

C1-10

Accel/Decel Setting Resolution

0 or 1

0

No.

Parameter Name

Setting Range

Default

C1-12

Motor 2 Acceleration Time

0.00 to 600.00 s

1.00

C1-13

Motor 2 Deceleration Time

0.00 to 600.00 s

1.00

No.

Parameter Name

Setting Range

Default

C1-15

<1> The setting range and default value depend on the display units set in parameter o1-03. If o1-03 is set between 0 and 4, the time required to go

from 0% speed to 100% maximum speed is expressed in seconds. If o1-03 is set to 5 or 6, then setting units will appear in m/s

2

or ft/s

2

. If the

drive is in V/f control mode, the inspection deceleration ramp can be set in seconds only.

Inspection Deceleration Ramp

0.00 to 2.00 s

<1>

0.00 s

<1>

No.

Parameter Name

Setting Range

Default

C2-01

Jerk at Accel Start

<1> The setting range and default value depend on the display units set in parameter o1-03. If o1-03 is set between 0 and 4, the time required to go

from 0% speed to 100% maximum speed is expressed in seconds. If o1-03 is set to 5 or 6, then setting units will appear in m/s

2

or ft/s

2

.

0.00 to 10.00 s

<1>

0.50 s

<1>

C2-02

Jerk at Accel End

C2-03

Jerk at Decel Start

C2-04

Jerk at Decel End

C2-05

Jerk below Leveling Speed

Advertising