186

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

5.6 F: Option Settings

5.6 F: Option Settings

F1: Encoder/PG Feedback Settings

The F1 parameters are used to set the drive up for operation using a motor encoder option card. Note that all speed
feedback option cards must be connected to the CN5-C port.

F1-01:

Encoder 1 Resolution

Sets the encoder resolution.

F1-02, F1-14: PG Open (PGo) Circuit Operation Selection, Detection Time

A PGo fault is triggered if the drive receives no pulse signal for longer than the time set in F1-14. Set the stopping method
for a PGo fault in parameter F1-02.

Parameter F1-02 Settings:
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only

Note: Due to potential damage to motor and machinery, the “Alarm only” setting should be used only under special circumstances.

F1-03, F1-08, F1-09: Overspeed (oS) Operation Selection, Detection Level, Delay Time

An oS fault is triggered when the speed feedback exceeds the value set in F1-08 for longer than the time set in F1-09. Set
the stopping method for an oS fault in parameter F1-03.

Parameter F1-03 Settings:
Setting 0: Ramp to stop (uses the deceleration ramp set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop ramp set to C1-09)
Setting 3: Alarm only

Note: Due to potential damage to motor and machinery, refrain from using the “Alarm only” setting except under special circumstances.

F1-04, F1-10, F1-11: Operation at Speed Deviation (dEv), Detection Level, Delay Time

A speed deviation error (dEv) is triggered when the difference between the speed reference and the speed feedback
exceeds the value set in F1-10 for longer than the time set in F1-11. The stopping method when a speed deviation fault
occurs can be selected in parameter F1-04.

No.

<1> In CLV/PM mode, the maximum setting is 15000 ppr.

Parameter Name

Setting Range

Default

F1-01

Encoder 1 Resolution

1 to 60000 ppr

<1>

Determined by A1-02

No.

Parameter Name

Setting Range

Default

F1-02

Operation Selection at PG Open Circuit (PGo)

0 to 3

1

F1-14

PG Open-Circuit Detection Time

0.0 to 10.0 s

2.0 s

No.

Parameter Name

Setting Range

Default

F1-03

Operation Selection at Overspeed (oS)

0 to 3

1

F1-08

Overspeed Detection Level

0 to 120%

115%

F1-09

Overspeed Detection Delay Time

0.0 to 2.0 s

0.0 s