5.7 H: Terminal Functions

202

YASKAWA ELECTRIC SIEP YAIL1E 01A YASKAWA AC Drive L1000E Technical Manual

Setting B, 18: Torque detection 1, Torque detection 2

These digital output functions to signal an overtorque or undertorque situation to an external device.

Set up the torque detection levels and select the output function from the table below.

Refer to L6: Torque Detection on

page 222

for details.

Setting E: Fault

The output closes when the drive faults (excluding CPF00 and CPF01 faults).

Setting F: Not used (Through mode)

Select this setting when using the terminal in a pass-through mode. When set to F, an output does not trigger any function
in the drive. Setting F, however, still allows the output status to be read by a PLC via a communication option or
MEMOBUS/Modbus communications.

Setting 10: Minor fault

Output closes when a minor fault condition is present.

Setting 11: Fault reset command active

Output closes whenever there is an attempt to reset a fault situation from the control circuit terminals, via serial
communications, or using a communications option card.

Setting 12: Timer output

This setting configures a digital output terminal as output for the timer function.

Refer to b4: Delay Timers on page 159

for details.

Setting 13: Speed agree 2 (f

ref

/f

out

agree 2)

Closes whenever the actual output speed or motor speed (CLV, CLV/PM) is within the speed agree width (L4-04) of the
current speed reference, regardless of the direction.

Note: Detection works in both forward and reverse.

Figure 5.23

Figure 5.23 Speed Agree 2 Time Chart

Refer to L4-03, L4-04: Speed Agreement Detection Level and Detection Width (+/-) on page 220

for more details.

Setting

Status

Description

B

Closed

Torque detection 1:
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-02 for longer than
the time specified in parameter L6-03.

18

Closed

Torque detection 2:
Output current/torque exceeds (overtorque detection) or is below (undertorque detection) the torque value set in parameter L6-05 for longer than
the time specified in parameter L6-06.

Status

Description

Open

Output speed or motor speed does not match the speed reference while the drive is running.

Closed

Output speed or motor speed is within the range of speed reference ±L4-04.

L4-04

L4-04

Speed
reference

Speed Agree 2

ON

OFF

Output speed

or motor speed