b: Application

The following settings are made with the application parameters (B parameters): operation method selection,
DC injection braking, speed searching, timer functions, dwell functions, and energy saving functions.

„

b1: Operation Mode Selection

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

b1-01

Frequency Refer-
ence Selection

Selects the frequency reference input
source.
0: Operator - Digital preset speed U1-01

or d1-01 to d1-17.

1: Terminals - Analog input terminal A1

(or terminal A2 based on parameter
H3-09).

2: Serial Com - Modbus RS-422/485 ter-

minals R+, R-, S+, and S-.

3: Option PCB - Option card connected

on 2CN.

0 to 3

1

No

Q

Q

Q

180H

4-4
6-2

6-67
6-84

Reference Source

b1-02

Run Command
Selection

Selects the Run Command input source.
0: Operator - RUN and STOP keys on

digital operator.

1: Terminals - Contact closure on termi-

nals S1 or S2.

2: Serial Com - Modbus RS-422/485 ter-

minals R+, R-, S+, and S-.

3: Option PCB - Option card connected

on 2CN.

0 to 3

1

No

Q

Q

Q

181H

4-4
6-8

6-67
6-84

Run Source

b1-03

Stopping Method
Selection

Selects the stopping method when the
Run Command is removed.
0: Decelerate to stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast with Timer (A new Run Com-

mand is ignored if received before the
timer expires).

0 to 3

*1

0

No

Q

Q

Q

182H

4-4

6-11

Stopping Method

b1-04

Reverse Opera-
tion Selection

Determines the forward rotation of the
motor, and if reverse operation is dis-
abled.
0: Reverse enabled.
1: Reverse disabled.

0 or 1

0

No

A

A

A

183H

6-55

Reverse Oper

b1-05

Minimum Output
Frequency (E1-
09) or Less Oper-
ation Selection

Operation method when frequency refer-
ence is less than minimum output fre-
quency set in E1-09.
0: Operates according to frequency ref-

erence (E1-09 is disabled).

1: Output shuts off (coast to stop if less

than E1-09).

2: Operates according to E1-09 (fre-

quency reference set to E1-09).

3: Zero speed (frequency reference

becomes zero when less than E1-09).

0 to 3

0

No

No

No

A

184H

6-11

Zero-Speed Oper

b1-06

Digital Input Scan
Time

Sets the scan rate of digital input termi-
nals.
0: 2 ms - 2 scans (for quick response)
1: 5 ms - 2 scans (for noisy environ-

ments)

0 or 1

1

No

A

A

A

185H

-

Cntl Input Scans