Installing and Wiring Option Cards

2-

31

„

Wiring the PG-X2

Wiring examples for the PG-X2 are provided in the following illustrations.

•

Shielded twisted-pair wires must be used for signal lines.

•

Do not use the pulse generator power supply for anything other than the pulse generator (encoder).
Using it for another purpose can cause malfunctions due to noise.

•

The length of the pulse generator wiring must not be more than 100 meters.

•

The direction of rotation of the PG can be set in parameter F1-05 (PG Rotation). The factory preset is
Phase A leads with a forward run command.

Fig 2.27 PG-X2 Wiring

IMPORTANT

Be sure that the ground terminal is properly grounded using a wire of the recommended size.
200 V class: Ground to 100

Ω or less 400 V class: Ground to 10 Ω

or less