Acceleration and Deceleration Characteristics

6-

21

‹

Preventing the Motor from Stalling during Acceleration (Stall Prevention
during Acceleration Function)

The Stall Prevention during Acceleration function prevents the motor from stalling if a heavy load is placed on
the motor and also during sudden rapid acceleration.

If L3-01 is set to 1 (enabled) and the MxC output current exceeds the -15% level of L3-02, then the accelera-
tion rate will begin to slow down. Acceleration will stop if the output current rises above L3-02.

When L3-01 is set to 2, then the motor will accelerate to the value set in L3-02 as the MxC automatically
adjusts the rate of acceleration to prevent stalling. Here, the acceleration time setting is disregarded.

„

Related Parameters

* Not available for the MxC models CIMR-ACA4110 and 4160 for V/f Control.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

L3-01

*

Stall Prevention
Selection During
Accel

Selects the stall prevention method used to
prevent excessive current during acceleration.
0: Disabled. - Motor accelerates at active

acceleration rate. The motor may stall if
load is too heavy or accel time is too short.

1: General Purpose - When output current

exceeds L3-02 level, acceleration stops.
Acceleration will continue when the out-
put current level falls below the L3-02
level.

2: Intelligent - The active acceleration rate is

ignored. Acceleration is completed in the
shortest amount of time without exceeding
the current value set in L3-02.

0 to 2

1

No

A

A

No

StallP Accel Sel

L3-02

Stall Prevention
Level During
Acceleration

This function is enabled when L3-01 is “1” or
“2”.
MxC rated current is 100%. Decrease the set
value if stalling or excessive current occurs
with default.

0 to 200

150%

No

A

A

No

StallP Accel Lvl

L3-03

Stall Prevention
Limit During
Acceleration

Sets the lower limit for stall prevention during
acceleration as a percentage of the rated cur-
rent of the MxC when operation is in the fre-
quency range above E1-06 (constant power
region).

0 to 100

50%

No

A

A

No

StallP CHP Lvl