Individual Functions

6-

107

When E1-03 is set to F (User-defined V/f pattern), parameters E1-04 to E1-10. If E1-03 can be set to anything
other than F, you can only refer to parameters E1-04 to E1-10. If the V/f characteristics are linear, set E1-07
and E1-09 to the same value. In this case, E1-08 will be ignored.

Fig 6.66 User-Set V/f Pattern

„

Setting Precautions

When the setting is to user-defined V/f pattern, beware of the following points.

When changing control method, parameters E1-07 to E1-10 will change to the defaults for that control
method.

Be sure to set the four frequencies as follows:
E1-04 (FMAX)

≥ E1-06 (FA) > E1-07 (FB) ≥ E1-09 (FMIN)

Output voltage (V)

E1-05

(VMAX)

E1-13

(V Base)

E1-08

(VC)

E1-10

(VMIN)

E1-09

(FMIN)

E1-07

(FB)

E1-06

(FA)

E1-04

(FMAX)

Frequency (Hz)