Yaskawa Matrix Converter User Manual
Page 175
Advertising
6
-10
Fig 6.11 3-Wire Sequence Time Chart
INFO
1. Use a sequence that switches terminal S1 on for 50 ms or longer for the Run Command. This will make the
Run Command self-holding in the MxC.
2. Before setting the 3-wire sequence, set the parameters for the multi-function input terminals, and then wire
the control circuit. If not, the motor might rotate unexpectedly and could cause injury or damage.
50 ms min.
Run Command
Forward/Reverse
Command
Motor speed
Can be either on or off
off
(stopped)
off (forward)
on (reverse)
Stop
Forward
Reverse
Stop
Forward
Stop Command