6

-38

Machine Protection

This section explains functions for protecting the machine.

‹

Reducing Noise and Leakage Current

The switching frequency of the output transistors in the MxC can be changed to reduce carrier noise and leak-
age current from the motor.

„

Related Parameters

* 1. Fixed to 2:4 kHz for V/f.

For Open Loop Vector Control, can select from 2:4 kHz or 4:8 kHz (Fixed to 2: 4 kHz for a 200 V class MxC for 45 kW and a 400 V class MxCs for 22

kW and 45 kW).

* 2. Fixed to 2: 4 kHz for 400 V class MxCs for 110 kW and 160 kW.

„

Control Method and Carrier Frequency Settings

Carrier frequency settings are restricted as listed in the following table according to the control method selec-
tion.

* Fixed to 2: 4 kHz for 200 V class MxC for 45 kW and 400 V class MxCs for 22 kW and 45 kW
Note: 1. Fixed to 2: 4 kHz for 400 V class MxCs for 110 kW and 160 kW.

2. The upper limit of the carrier frequency depends on the MxC capacity.

„

Carrier Frequency Setting Precautions

When selecting the carrier frequency, observe the following precautions.

Adjust the carrier frequency according to the cases shown below.
If the wiring distance between MxC and motor is long: Set the carrier frequency low. (Use the following
values as guidelines.)

If speed and torque are inconsistent at low speeds: Lower the carrier frequency.
If there is too much leakage current from the MxC: Lower the carrier frequency.
If the metallic noise from the motor is too loud: Raise the carrier frequency.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

C6-02

Carrier Frequency
Selection

Select carrier frequency pattern.
2: 4 kHz
4: 8 kHz
6: 12 kHz

2, 4, or

6

*1 *2

2

No

Q

Q

Q

CarrierFreq Sel

Control Method

Carrier Frequency

V/f Control

2: 4.0 kHz

Open Loop Vector Control

2: 4.0 kHz
4: 8.0 kHz

*

Flux Vector Control

2: 4.0 kHz
4: 8.0 kHz
6: 12.0 kHz

Wiring Length

50 m or less

100 m or less

Over 100 m

C6-02 (Carrier Frequency
Selection) setting

2, 4, or 6

(4, 8, or 12 kHz)

2 or 4

(4 or 8 kHz)

2 (4 kHz)