H3: analog inputs – Yaskawa Matrix Converter User Manual

Page 139

Advertising
background image

Parameter Tables

5-

39

„

H3: Analog Inputs

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

H3-01

Terminal A1 Sig-
nal Level Selec-
tion

Sets the signal level of terminal A1.
0: 0 to 10VDC
1: -10 to +10VDC

[11-bit plus polarity sign]

0 or 1

0

No

A

A

A

410H

6-25

Term A1 Lv1 Sel

H3-02

Terminal A1 Gain
Setting

Sets the output level when 10 V is input,
as a percentage of the maximum output
frequency (E1-04).

0.0 to

1000.0

100.0

%

Yes

A

A

A

411H

6-25

Terminal A1 Gain

H3-03

Terminal A1 Bias
Setting

Sets the output level when 0 V is input, as
a percentage of the maximum output
frequency (E1-04).

-100.0

to

+100.0

0.0%

Yes

A

A

A

412H

6-25

Terminal A1 Bias

H3-04

Terminal A3 Sig-
nal Level Selec-
tion

Sets the signal level of terminal A3.
0: 0 to 10 VDC
1: -10 to +10 VDC

0 or 1

0

No

A

A

A

413H

6-25

6-108

Term A3 Signal

H3-05

Terminal A3
Function Selec-
tion

Select multi-function analog input func-
tion for terminal A3. Refer to the next
page.

0 to 1F

2

No

A

A

A

414H

6-25

6-108

Terminal A3 Sel

H3-06

Terminal A3 Gain
Setting

Sets the output level when 10 V is input.

0.0 to

1000.0

100.0

%

Yes

A

A

A

415H

6-25

6-109

Terminal A3 Gain

H3-07

Terminal A3 Bias
Setting

Sets the frequency reference when 0 V is
input.

-100.0

to

+100.0

0.0%

Yes

A

A

A

416H

6-25

6-109

Terminal A3 Bias

H3-08

Terminal A2 Sig-
nal Level Selec-
tion

Selects the signal level of terminal A2.
0: 0 to 10 VDC (switch S1-2 must be in

the off position).

1: -10 to +10 VDC (switch S1-2 must

be in the off position).

2: 4 to 20 mA (switch S1-2 must be in

the on position)

Note: Switch between current or voltage

inputs by using (S1-2) switch on

the terminal board.

0 to 2

2

No

A

A

A

417H

6-25

6-109

Term A2 Signal

H3-09

Terminal A2
Function Selec-
tion

Select multi-function analog input func-
tion for terminal A2. Refer to the next
table.

0 to 1F

0

No

A

A

A

418H

6-25

6-109

Terminal A2 Sel

H3-10

Terminal A2 Gain
Setting

Sets the output level when 10V is input.

0.0 to

1000.0

100.0

%

Yes

A

A

A

419H

6-25

6-109

Terminal A2 Gain

H3-11

Terminal A2 Bias
Setting

Sets the output level when 0V is input.

-100.0

to

+100.0

0.0%

Yes

A

A

A

41AH

6-25

6-109

Terminal A2 Bias

H3-12

Analog Input Fil-
ter Time Constant

This parameter adjusts the filter on all 3
analog inputs. Increase to add stability,
decrease to improve response.

0.00 to

2.00

0.03

s

No

A

A

A

41BH

4-17
6-26

Filter Avg Time