6

-78

Motor Overload (OL1) Pre-Alarm (Setting: 1F)

This output function is valid when the motor overload protection function is enabled (L1-01 =1).

This output can be used to warn of overheating before the protection function itself operates.

MxC Overheat (OH) Pre-Alarm (Setting: 20)

This output function indicates that the temperature of the cooling fins reaches the temperature set in L8-02
(Overheating Alarm Level).

Speed Reference Limit (Setting: 31)

Zero-Servo End (Setting: 33)

This output function indicates that zero-servo position control has been completed.

The output is turned on after the Zero-Servo Command is input and the difference between the zero-servo
operation starting position and the current position is within the Zero Servo Completion Width (b9-02).

off

The motor protection function's electronic thermal value is less than 90% of the detection level.

on

The motor protection function's electronic thermal value is greater than 90% of the detection level.

off

The cooling fin temperature is less than the “OH Pre-Alarm Level” set in L8-02.

on

The cooling fin temperature exceeds the “OH Pre-Alarm Level” set in L8-02.

off

Any time this switch in not on.

on

Enables the speed reference limit in the following conditions (in Flux Vector Control):

1. Frequency reference

≥ Frequency Reference Upper Limit (d2-01)

Frequency reference

≤ Frequency Reference Lower Limit (d2-02)

Frequency reference

≥ Output frequency lower limit of the multi-function analog input

(Setting: 9)

2. The frequency reference is less than the Min. Output Frequency (E1-09), and b1-05 is set to 1,

2, or 3.

off

The Zero-Servo Command isn’t being input or zero-servo position control hasn’t been completed.

on

The position has been brought within the Zero Servo Completion Width (b9-02) after the Zero-Servo
Command was input.