C5: speed control (asr), C6: carrier frequency – Yaskawa Matrix Converter User Manual

Page 119

Advertising
background image

Parameter Tables

5-

19

„

C5: Speed Control (ASR)

* The default will change when the control method is changed. These values are the defaults for the Flux Vector Control.

„

C6: Carrier Frequency

* 1. Fixed to 2:4 kHz for V/f.

For Open Loop Vector Control, can select from 2:4 kHz or 4:8 kHz (Fixed to 2: 4 kHz for 200 V class MxC for 45 kW and 400 V class MxCs for 22 kW and 45

kW).

* 2. Fixed to 2: 4 kHz for 400 V class MxCs for 110 kW and 160 kW.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

C5-01

ASR Propor-
tional Gain 1

Sets the proportional gain of the speed
control loop (ASR).

0.00 to
300.00

20.00

*

Yes

No

No

A

21BH

4-15

6-116

ASR P Gain 1

C5-02

ASR Integral
Time 1

Sets the integral time of the speed control
loop (ASR).

0.000 to

10.000

0.500

s

*

Yes

No

No

A

21CH

4-15

6-116

ASR I Time 1

C5-03

ASR Propor-
tional Gain 2

Sets the speed control gain 2 and integral
time 2 of the speed control loop (ASR).
Note: Adjustment is not normally

required.

0.00 to
300.00

20.00

*

Yes

No

No

A

21DH

4-15

6-116

ASR P Gain 2

C5-04

ASR Integral
Time 2

0.000 to

10.000

0.500

s

*

Yes

No

No

A

21EH

4-15

6-116

ASR I Time 2

C5-06

ASR Primary
Delay Time Con-
stant

Sets the filter time constant for the time
from the speed loop to the Torque Com-
mand output.

0.000 to

0.500

0.004

s

*

No

No

No

A

220H

4-15

6-116

ASR Delay Time

C5-07

ASR Gain
Switching Fre-
quency

Sets the frequency for switching between
Proportional Gain 1, 2 and Integral Time
1, 2.

0.0 to
120.0

0.0 Hz

No

No

No

A

221H

4-15

6-116

ASR Gain SW
Freq

C5-08

ASR Integral
Limit

Sets the ASR integral upper limit and
rated load as a percentage of maximum
output frequency (E1-04).

0 to 400 400%

No

No

No

A

222H

6-116

ASR I Limit

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

C6-02

Carrier Fre-
quency Selection

Select carrier frequency pattern.
2: 4 kHz
4: 8 kHz
6: 12 kHz

2, 4, or

6

*1 *2

2

No

Q

Q

Q

224H

4-4

6-38

CarrierFreq Sel

P, I

0

E1-04

Motor speed (Hz)

P=C5-01
I=C5-02

P=C5-03
I=C5-04