Copying Parameters

The digital operator can perform the following three functions using the built-in EEPROM (non-volatile mem-
ory).

Store MxC parameter set values in the digital operator (READ)

Write parameter set values stored in the digital operator to the MxC (COPY)

Compare parameter set values stored in the digital operator with MxC parameters (VERIFY)

„

Related Parameters

IMPORTANT

The Matrix Converter is displayed as MxC, and the digital operator is displayed as OP while executing the
COPY function.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

o3-01

Copy Function
Selection

This parameter controls the copying of
parameters to and from the digital operator.
0: COPY SELECT (no function)
1: INV → OP READ: All parameters are

copied from the MxC to the digital opera-
tor.

2: OP → INV WRITE: All parameters are

copied from the digital operator to the
MxC.

3: OP⇔INV VERIFY: Parameter settings in

the MxC are compared to those in the dig-
ital operator.

Note: When using the copy function, the MxC

model number (o2-04), software num-

ber (U1-14), and control method (A1-

02) must match or an error will occur.

0 to 3

0

No

A

A

A

Copy Function Sel

o3-02

Copy Allowed
Selection

Enables and disables the digital operator copy
functions.
0: Disabled. - No digital operator copy func-

tions are allowed.

1: Enabled. - Copying allowed.

0 or 1

0

No

A

A

A

Read Allowable