Specifications for Options and Peripheral Devices

9-

5

Specifications for Options and Peripheral Devices

The following options and peripheral devices can be used for the MxC. Select them according to the
application.

* 1. Use an earth leakage breaker that has harmonics protection and a minimum current of 30 mA per MxC. Otherwise, the harmonic leakage current may cause a mal-

function. If a malfunction occurs in an earth leakage breaker without harmonic protection, lower the carrier frequency of MxC, replace the earth leakage breaker

with one that has harmonic protection, or raise the current of the earth leakage breaker to 200 mA or more per MxC.

* 2. The FINEMET zero-phase reactor is manufactured by Hitachi Metals.

Table 9.4 Options and Peripheral Devices

Purpose

Name

Model (Code)

Descriptions

Protect MxC
wiring

MCCB or
Ground Fault
Interrupter

*1

NF†

Always connect a breaker to the power supply line to
protect MxC wiring. Use a ground fault interrupter
suitable for high frequencies.

Prevents burning
of the MxC.

Magnetic Con-
tactor

SC series

Install to prevent the MxC from burning out when
faults occur at the input terminal side of the MxC.
Always attach a surge absorber to the coil.

Contains switch-
ing surge

Surge Absorber

DCR2-†

Absorbs surge from the magnetic contactor and con-
trol relays. Connect surge absorbers to all magnetic
contactors and relays near the MxC.

Isolates I/O
signals

Isolator

DGP†

Isolates the I/O signals of the MxC and is enabled
against inductive noise.

Reduces the
affects of radio
and
control device
noise

Input Noise
Filter

LNFD-†
FN-†

Reduces noise coming into the MxC from the power
supply line and to reduce noise flowing from the
MxC into the power supply line. Connect as close to
the MxC as possible.

FINEMET
zero-phase
reactor to reduce
radio noise

*2

F6045GB
(FIL001098)
F11080GB
(FIL001097)
F200160BP
(300-001-041)

Reduces noise from the line that sneaks into the MxC
input power system. Insert as close to the MxC as
possible.
Can be use on both the input side and output side.

Output Noise
Filter

LF-†

Reduces noise generated by the MxC. Connect as
close to the MxC as possible.

Operates the MxC
externally

VS Operator
(small plastic
Operator)

JVOP-95•†
(73041-0905X-†)

Allows frequency reference settings and on/OFF
operation control to be performed by analog refer-
ences from a remote location (50 m max).
Frequency counter specifications: 60/120 Hz, 90/
180Hz

VS Operator
(Standard
steel-plate
Operator)

JVOP-96•†
(73041-0906X-†)

Allows frequency reference settings and on/OFF
operation control to be performed by analog refer-
ences from a remote location (50 m max).
Frequency counter specifications: 75 Hz, 150 Hz,
220 Hz

Digital Operator
Connection
Cable

1 m cable:
(72606-WV001)
3 m cable:
(72606-WV003)

Extension cable to use a digital operator remotely.
Cable length: 1 m or 3 m

Controls an MxC
system

VS System
Module

JGSM-†

A system controller that can be match to the auto-
matic control system to produce an optimum system
configuration.

Saves the momen-
tary power loss
compensation
time of MxC

Momentary
power loss com-
pensation unit

P00†0
(73600-P00†0)

Safety measure taken to protect against momentary
power loss of the control power supply.

Set/monitor
frequencies and
voltages
externally.

Frequency Meter DCF-6A

Devices to set or monitor frequencies externally.

Frequency Setter

RV30YN20S
(2 k

Ω)

Frequency Set-
ter Knob

CM-3S

Output Voltmeter SCF-12NH

Measures the output voltage externally and designed
for use with a PWM MxC.

Correct frequency
reference input,
frequency meter,
ammeter scales

Variable
Resistor Board
for Frequency
Reference

2 k

Ω

(ETX003270)
20 k

Ω

(ETX003120)

Connected to the control circuit terminals to input a
frequency reference.

Frequency Meter
Scale Correction
Resistor

(RH000850)

Calibrates the scale of frequency meters and amme-
ters.

Power
supply

Molded-case
circuit breaker
or ground fault
interrupter

Magnetic
contactor
(MC)

Motor

Ground

Input noise
filter

Output noise
filter

MxC

Ground

Zero phase
reactor

Zero phase
reactor