Parameter Tables

5-

35

* The defaults in the parentheses are for 3-wire sequence.

Multi-Function Contact Input Functions

H1-09

Multi-Function
Digital Input Ter-
minal S11 Func-
tion Selection

Multi-function contact input 9

0 to 78

7

No

A

A

A

408H

-

Terminal S11 Sel

H1-10

Multi-Function
Digital Input Ter-
minal S12 Func-
tion Selection

Multi-function contact input 10

0 to 78

15

No

A

A

A

409H

-

Terminal S12 Sel

Set

Value

Function

Control

Methods

Page

V/f

Open

Loop

Vector

Flux

Vector

0

3-wire sequence (Forward/Reverse Run Command)

Yes

Yes

Yes

6-9

1

Local/Remote selection (ON: Operator, off: Parameter setting)

Yes

Yes

Yes

6-67

2

Option/MxC selection (ON: Option card)

Yes

Yes

Yes

6-74

6-141

3

Multi-step speed reference 1
When H3-09 (Multi-function analog input (terminal A2) function selection) is set to
0 (Auxiliary frequency reference), this function can be used with the master/auxiliary
speed switch.

Yes

Yes

Yes

6-5

4

Multi-step speed reference 2

Yes

Yes

Yes

6-5

5

Multi-step speed reference 3

Yes

Yes

Yes

6-5

6

Jog Frequency Command (higher priority than multi-step speed reference)

Yes

Yes

Yes

6-5

7

Accel/decel time 1

Yes

Yes

Yes

6-18

8

External baseblock NO (NO contact: Baseblock at on)

Yes

Yes

Yes

6-68

9

External baseblock NC (NC contact: Baseblock at off)

Yes

Yes

Yes

6-68

A

Accel/decel ramp hold (ON: Accel/decel stopped, frequency on hold)

Yes

Yes

Yes

6-69

B

OH2 alarm signal input (ON: OH2 will be displayed)

Yes

Yes

Yes

-

C

Multi-function analog input selection (ON: Enable)

Yes

Yes

Yes

-

E

Speed control integral reset (ON: Integral control disabled)

No

No

Yes

6-116

F

Not used (Set when a terminal is not used)

-

-

-

-

10

Up Command (Always set with the Down Command)

Yes

Yes

Yes

6-70

11

Down Command (Always set with the Up Command)

Yes

Yes

Yes

6-70

12

FJOG Command (ON: Forward run at jog frequency d1-17)

Yes

Yes

Yes

6-75

13

RJOG Command (ON: Reverse run at jog frequency d1-17)

Yes

Yes

Yes

6-75

14

Fault reset (Reset when turned on)

Yes

Yes

Yes

7-2

15

Emergency stop (Normally open condition: Decelerate to stop in deceleration time
set in C1-09 when on).

Yes

Yes

Yes

6-16

16

Motor Switch Command (Motor 2 selection)

Yes

Yes

Yes

-

17

Emergency stop (Normally closed condition: Decelerate to stop in deceleration time
set in C1-09 when off)

Yes

Yes

Yes

6-16

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector