Monitor Parameters

6-

81

Adjusting the Meter

The output voltage for terminals FM-AC and AM-AC and output channels 1 and 2 of the AO option card can
be adjusted while the MxC is stopped. For example, just pressing the ENTER key and displaying the data set-
ting display for H4-02 or H4-03 will cause the following voltage to be output by the FM-AC terminals.

10 V/100% monitor output

× output gain (H4-02) + output bias (H4-03)

Just pressing the ENTER key and displaying the data setting display for F4-02 or F4-05 will cause the follow-
ing voltage to be output to channel 1 of the AO option card.

10 V/100% monitor output

× output gain (F4-02) + output bias (F4-05)

Fig 6.56 Monitor Output Adjustment

„

Switching Analog Monitor Signal Levels

Monitor items corresponding to -10 V to +10 V output 0 to 10 V signals when the monitor value is positive
(+), and 0 to -10 V signals when the monitor value is negative (-). For monitor items corresponding to -10 V to
+10 V, refer to Chapter 5 Parameters and Settings.

INFO

Select the signal levels separately for multi-function analog output terminals and analog output option termi-
nals.

Output voltage

Gain

×10 V

Bias

× 10/100 V

Monitor item

10 V

0 V

0%

100%