Example of momentary power loss – Yaskawa Matrix Converter User Manual

Page 223

Advertising
background image

6

-58

„

Example of Momentary Power Loss

Figure 6.42 shows an example of what happens in the MxC if a momentary power loss occurs when: L2-01 is
set to 1, L2-02 to 0.5, L2-03 to 0.7, or b3-05 to 0.2.

If the power is restored within the momentary power loss ridethrough time, MxC will carry out speed search
and normal operation will automatically restart after completing the power resonance.

Fig 6.42 Example when Momentary Power Loss Occurs

If the momentary power loss time is longer than the momentary power loss ridethrough time, an FDV alarm
(Power Supply Frequency Fault) will occur and the MxC will stop the operation.

Power-supply status

Control power voltage

Power error detection time:

Approx. 2 ms

MxC operation status

Normal operation

Baseblock

∗2

(BB)

Speed search

Normal operation

Min. baseblock time

Speed search

waiting time

Power error detected

(L2-03) : 0.7 s

(b3-05) : 0.2 s

Power resonance time

Momentary power loss time

UV level

∗1

* 1. The baseblock will be released after completing L2-03, UV time, b3-05,

and the power resonance time.

* 2. The motor will be in coasting to a stop during baseblock. Take measures

if there is possibility that the coasting to a stop cause the problem.