Limiting motor rotation direction, Operation during motor overheat, Related parameters – Yaskawa Matrix Converter User Manual

Page 220

Advertising
background image

Machine Protection

6-

55

„

Operation during Motor Overheat

Set the operation if the motor overheats in parameters L1-03 and L1-04. Set the motor temperature input filter
time constant in L1-05. If the motor overheats, the OH3 and OH4 error codes will be displayed on the digital
operator.

Error Codes If the Motor Overheats

By setting H3-09 (Terminal A2 Function Selection) or H3-05 (Terminal A3 Function Selection) to E (Motor
temperature input), alarm OH3 or OH4 will occur using the PTC temperature-resistance characteristics, and
protect the motor. The terminal connections are shown in the following diagram.

Fig 6.41 Mutual Connections During Motor Overheating Protection

‹

Limiting Motor Rotation Direction

If the motor reverse rotation is prohibited, a Reverse Run Command will not be accepted even if it is input.
Use this setting for applications in which reverse motor rotation can cause problems (e.g., fans, pumps, etc.).

„

Related Parameters

Error Code

Details

OH3

MxC stops or continues to operate, according to the setting in L1-03.

OH4

MxC stops according to the setting in L1-04.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

b1-04

Reverse Operation
Selection

Determines the forward rotation of the motor,
and if reverse operation is disabled.
0: Reverse enabled.
1: Reverse disabled.

0 or 1

0

No

A

A

A

Reverse Oper

MxC

Multi-function
contact input

Branch resistance
18 k

Ω

PTC thermistor

Multi-function
contact output

Fault contact output

Multi-function
PHC output

+ V
(+15 V, 20 mA)

A3
(0-10 V)

AC

M1

M2

MA

MB

MC

P1

P2

PC

Advertising