Yaskawa Matrix Converter User Manual

Page 345

Advertising
background image

7

-24

„

The voltage tolerance between motor phases is insufficient.

When the motor is connected to the MxC output, a surge is generated between the MxC switching and the
motor coil. Normally the maximum surge voltage is three times the MxC's input power supply voltage (i.e.,
1,200 V for 400 V class). Be sure to use a motor with a voltage tolerance between motor phases that is greater
than the maximum surge voltage. In particular, when using a 400 V class MxC, use a special motor for invert-
ers.

„

Auto-Tuning has not been performed for Open Loop Vector Control.

Open Loop Vector Control will not operate the motor if Auto-Tuning has not yet been performed. Perform
Auto-Tuning, or calculate and set the motor parameters manually. Alternatively, change the Control Method
Selection to the V/f Control Method (A1-02 = 0).

‹

Noise is Produced from an AM Radio or when the MxC is Started

If noise is generated by MxC switching, then take the following action:

•

Change the MxC's Carrier Frequency Selection (C6-02) to lower the carrier frequency. This will help to
some extent by reducing the amount of internal switching.

•

Install an Input Noise Filter at the MxC's power supply input area.

•

Install an Output Noise Filter at the MxC's power supply output area.

•

Use metal tubing. Electric waves can be shielded by metal, so encase the MxC with metal (steel).

•

Ground the MxC and motor.

•

Separate main circuit wiring from control wiring.

‹

Ground Fault Interrupter Operates while the MxC is Running

The MxC performs internal switching, so there is a certain amount of leakage current. This may cause the
ground fault interrupter to operate and cut off the power supply. Change to a ground fault interrupter with a
high leakage detection level (i.e., a sensitivity current of 200 mA or greater per Unit, with an operating time of
0.1 s or more), or one that incorporates high frequency countermeasures (i.e., one designed for use with
inverter). It will also help to some extent to change the MxC’s Carrier Frequency Selection (C6-02) to lower
the carrier frequency. In addition, remember that the leakage current increases as the cable is lengthened.

Advertising