o2: Multi-function Selections

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

o2-01

Local/Remote
Key Function
Selection

Determines if the digital operator
LOCAL/REMOTE key is functional.
0: Disabled.
1: Enabled.

0 or 1

1

No

A

A

A

505H

6-125

Local/Remote
Key

o2-02

STOP Key Func-
tion Selection

Determines if the STOP key on the digital
operator will stop the MxC when MxC is
operating from external terminals or
serial communication.
0: Disabled.
1: Enabled.

0 or 1

1

No

A

A

A

506H

6-125

Oper STOP Key

o2-03

User Parameter
Default Value

Allows storing of parameter settings as a
User Initialization Selection.
0: No Change
1: Set Defaults - Saves current parame-

ter settings as user initialization. A1-
03 now allows selecting <1110> for
user initialization and returns o2-03 to
zero.

2: Clear All - Clears the currently saved

user initialization. A1-03 no longer
allows selecting <1110> and returns
o2-03 to zero.

0 to 2

0

No

A

A

A

507H

4-13

6-126

User Defaults

o2-04

MxC/kVA Selec-
tion

This parameter only needs to be set when
installing a new control board. Do not
change for any other reason.

0 to FF

5

*1

No

A

A

A

508H

-

MxC Model #

o2-05

Frequency Refer-
ence Setting
Method Selection

Determines if the DATA/ENTER key
must be used to input a frequency refer-
ence from the digital operator.
0: Disabled. - DATA/ENTER key must

be pressed to enter a frequency refer-
ence.

1: Enabled. - DATA/ENTER key is not

required. The frequency reference is
adjusted by the up and down arrow
keys on the digital operator without
having to press the DATA/ENTER
key.

0 or 1

0

No

A

A

A

509H

6-126

Operator M.O.P.

o2-06

Operation Selec-
tion when Digital
Operator is Dis-
connected

Determines if the MxC will stop when the
digital operator is removed when in Local
Mode or b1-02 = 0.
0: Disabled. - The MxC will not stop

when the digital operator is removed.

1: Enabled. - The MxC will fault (OPR)

and coast to stop when the digital
operator is removed.

0 or 1

0

No

A

A

A

50AH

-

Oper Detection

o2-07

Cumulative Oper-
ation Time Setting Sets the initial value of the elapsed opera-

tion timer U1-13.

0 to

65535

0 hr

No

A

A

A

50BH

6-126

Elapsed Time Set

o2-08

Cumulative Oper-
ation Time Selec-
tion

Sets how time is accumulated for the
elapsed operation timer U1-13.
0: Power-On Time. Time accumulates

when the MxC is powered.

1: Running Time. Time accumulates

only when the MxC is running.

0 or 1

0

No

A

A

A

50CH

-

Elapsed Time Run