D2: reference limits – Yaskawa Matrix Converter User Manual

Page 121

Advertising
background image

Parameter Tables

5-

21

* The upper limit of the setting range depends on the upper limit set at E1-04. The maximum allowable setting is 120.00.

„

d2: Reference Limits

d1-13

Frequency
Reference 13

The frequency reference when multi-step
speed references 3 and 4 are on for multi-
function inputs (unit: Set in o1-03).

0.00 to
120.00

*

0.00

Hz

Yes

A

A

A

28EH

-

Reference 13

d1-14

Frequency
Reference 14

The frequency reference when multi-step
speed references 1, 3, and 4 are on for
multi-function inputs (unit: Set in o1-03).

0.00

Hz

Yes

A

A

A

28FH

-

Reference 14

d1-15

Frequency
Reference 15

The frequency reference when multi-step
speed references 2, 3, and 4 are on for
multi-function inputs (unit: Set in o1-03).

0.00

Hz

Yes

A

A

A

290H

-

Reference 15

d1-16

Frequency
Reference 16

The frequency reference when multi-step
speed references 1, 2, 3, and 4 are on for
multi-function inputs (unit: Set in o1-03).

0.00

Hz

Yes

A

A

A

291H

-

Reference 16

d1-17

Jog Frequency
Reference

The frequency reference when the jog
frequency reference selection, FJOG
command, or RJOG command is on (unit:
Set in o1-03).

6.00

Hz

Yes

Q

Q

Q

292H

4-4
6-5

6-75

Jog Reference

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

d2-01

Frequency Refer-
ence Upper Limit

Set the output frequency upper limit as a
percent, taking the max. output frequency
to be 100%.

0.0 to

110.0

100.0

%

No

A

A

A

289H

6-30
6-70

Ref Upper Limit

d2-02

Frequency Refer-
ence Lower Limit

Sets the output frequency lower limit as a
percentage of the maximum output fre-
quency.

0.0 to

110.0

0.0%

No

A

A

A

28AH

6-30
6-70

Ref Lower Limit

d2-03

Master Speed
Reference Lower
Limit

Set the master speed reference lower limit
as a percent, taking the max. output fre-
quency to be 100%.

0.0 to

110.0

0.0%

No

A

A

A

293H

6-30
6-70

Ref1 Lower Limit

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector