Individual functions, Using memobus communications – Yaskawa Matrix Converter User Manual

Page 247

Advertising
background image

6

-82

Individual Functions

This section explains the individual functions used in special applications.

‹

Using MEMOBUS Communications

The serial communications with MEMOCON-series Programmable Controllers (PLCs) or similar devices can
be performed using the MEMOBUS protocol.

„

MEMOBUS Communications Configuration

MEMOBUS communications are configured using 1 master (PLC) and a maximum of 31 slaves. Serial com-
munications between master and slave are normally started by the master, and the slave responds.

The master performs signal communications with one slave at a time. Consequently, be sure to set the address
of each slave beforehand, so the master can perform signal communications using that address. Slaves Receiv-
ing Commands from the master perform the specified function, and send a response to the master.

Fig 6.57 Example of Connections between PLC and MxC

„

Communications Specifications

The MEMOBUS communications specifications are shown in the following table.

Item

Specifications

Interface

RS-422, RS-485

Communications Cycle

Asynchronous (Start-stop synchronization)

Communications Parameters

Baud rate

Select from 1200, 2400, 4800, 9600, and 19200 bps.

Data length

8 bits fixed

Parity

Select from even, odd, or none.

Stop bits

1 bit fixed

Communications Protocol

MEMOBUS (RTU Mode only)

Number of Connectable Units 31 units max (when using RS-485)

MxC

MxC

MxC

MEMOCON-series PLC

RS-485 connections
example