Related Alarm Displays

When setting a multi-function contact output H2-†† to 2F, the alarm is displayed on the digital operator as
shown below.

* Applicable for the Varispeed AC with software versions PRG: 1050 or later.

‹

Settings Required After Replacement of Cooling Fan or Capacitors on
PCB Board

Set o2-10 to 0 after replacing the cooling fan.

Set o2-18 to 0 after replacing the PCB board.

Refer to Chapter 8 Maintenance and Inspection for the replacement procedure.

„

Related Parameters

* Applicable for Varispeed AC with software versions PRG: 1050 or later.

Display

Meaning

Probable Causes

Corrective Actions

LT-C

*

(flashing)

Maintenance

Monitor U1-61 has reached
100%.

The capacitors on the PCB board
have reached their estimated
maintenance time period.

Reset parameter o2-18 to “0%”
after replacing the capacitors on
the PCB board.

LT-F

*

(flashing)

Fan Maintenance

Monitor U1-63 has reached
100%.

The cooling fan has reached its
estimated maintenance time
period.

Replace the cooling fan and set
parameter o2-10 to “0H”.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Display

V/f

Open

Loop

Vector

Flux

Vector

o2-10

*

Fan operation
time setting

Set the initial value of the
fan operation time using
time units.
The operation time
accumulates from the set
value.

0 to

65535

0 hr

No

A

A

A

50EH

Fan ON Time Set

o2-18

*

Capacitor
maintenance
setting

Allows the user to set the
maintenance time for the
capacitors on the PCB board
(U1-61). The user can reset
the accumulated operation
time back to zero, or to some
other desired value.

0 to
150

0%

No

A

A

A

51DH

C MaintenanceSet