Continue running after frequency reference loss, Related parameters – Yaskawa Matrix Converter User Manual

Page 229

Advertising
background image

6

-64

Power Loss Time Longer than Minimum Baseblock Time

Fig 6.48 Speed Search After Baseblock (Current Detection: Loss Time > L2-03)

‹

Continue Running after Frequency Reference Loss

The frequency reference loss detection function continues operation using 80% speed of the frequency refer-
ence before loss when the frequency reference using an analog input is reduced 90% or more in 400 ms.

When the error signal during frequency reference loss is output externally, set H2-01 to H2-05 (Terminals M1-
M2, P1-PC, P2-PC, P3-C3, and P4-C4 Function Selection) to C (frequency reference lost).

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

L4-05

Frequency Refer-
ence Loss Detec-
tion Selection

0: Stop (Operation follows the frequency ref-

erence.)

1: Operation at 80% speed continues. (At

80% of speed before the frequency refer-
ence was lost)

Frequency reference is lost: Frequency refer-
ence dropped over 90% in 400 ms.

0 or 1

0

No

A

A

A

Ref Loss Sel

AC power supply

Output frequency

Output current

off

on

Output frequency before power loss

Set frequency
reference

Minimum Baseblock Time
(L2-03)

Deceleration speed set in b3-03

b3-02

Speed Search Deactivation Current

Speed search Delay time (b3-05)