Yaskawa Matrix Converter User Manual

Page 140

Advertising
background image

5

-40

H3-05, H3-09 Settings

Set

Value

Function

Contents (100%)

Control

Methods

Page

V/f

Open

Loop

Vector

Flux

Vector

0

Add to terminal A1

Maximum output frequency

Yes

Yes

Yes

6-27

6-109

1

Frequency gain

Frequency Reference (voltage) Command value

Yes

Yes

Yes

6-26

2

Auxiliary Frequency Reference 1 (2nd
step analog)

Maximum output frequency

Yes

Yes

Yes

6-5

3

Auxiliary Frequency Reference 2 (3rd
step analog)

Maximum output frequency

Yes

Yes

Yes

6-5

4

Voltage bias

200 V (200 V class), 400 V (400 V class)

Yes

No

No

-

5

Accel/decel change (reduction coeffi-
cient)

Set acceleration and deceleration times (C1-01 to
C1-08)

Yes

Yes

Yes

6-17

6

DC injection braking current

MxC rated output current

Yes

Yes

No

6-16

7

Overtorque/undertorque detection level

Motor rated torque for vector control
MxC rated output current for V/f control

Yes

Yes

Yes

6-50

8

Stall prevention level during run

MxC rated output current

Yes

No

No

6-44

9

Frequency reference lower limit level

Maximum output frequency

Yes

Yes

Yes

6-31

A

Jump frequency

Maximum output frequency

Yes

Yes

Yes

6-29

B

PID feedback

Maximum output frequency

Yes

Yes

Yes

6-97

C

PID target value

Maximum output frequency

Yes

Yes

Yes

6-97

D

Frequency bias 2

Maximum output frequency

Yes

Yes

Yes

6-27

E

Motor temperature input

10 V = 100%

Yes

Yes

Yes

6-55

10

Positive torque limit

Motor rated torque

No

Yes

Yes

6-41

11

Negative torque limit

Motor rated torque

No

Yes

Yes

6-41

12

Regenerative torque limit

Motor rated torque

No

Yes

Yes

6-41

13

Torque reference/torque limit at speed
control

Motor rated torque

No

No

Yes

6-109

14

Torque compensation

Motor rated torque

No

No

Yes

6-109

15

Positive/negative torque limit

Motor rated torque

No

Yes

Yes

6-41

1F

Analog input not used.

-

Yes

Yes

Yes

6-6

16 to 1E Not used

-

-

-

-

-

Advertising