Frequency reference, Selecting the frequency reference source – Yaskawa Matrix Converter User Manual

Page 167

Advertising
background image

6

-2

Frequency Reference

This section explains how to input and set the frequency reference to the MxC.

‹

Selecting the Frequency Reference Source

Set parameter b1-01 to select the frequency reference source.

„

Related Parameters

„

Entering the Frequency Reference from the Digital Operator

The frequency reference can be entered from the digital operator when b1-01 is set to 0.

Input the frequency reference from the frequency reference setting screen display.

For details on setting the frequency reference, refer to Chapter 3 Digital Operator and Modes.

Fig 6.1 Frequency Setting Display

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

b1-01

Frequency
Reference
Selection

Selects the frequency reference input
source.
0: Operator - Digital preset speed U1-01

or d1-01 to d1-17.

1: Terminals - Analog input terminal A1

(or terminal A2 based on parameter
H3-09).

2: Serial Com - Modbus RS-422/485 ter-

minals R+, R-, S+, and S-.

3: Option PCB - Option card connected

on 2CN.

0 to 3

1

No

Q

Q

Q

Reference
Source

-DRIVE-

Frequency Ref

U1-01= 0 0 0.0 0Hz

-DRIVE-

Rdy

Frequency Ref

U1-01= 0 0 0.0 0Hz

"0.00Hz"

(0.00

60.00)