Stopping Methods

6-

11

Stopping Methods

This section explains the parameter settings and functions to have the MxC stop the motor.

‹

Selecting the Stopping Method when a Stop Command is Sent

There are four methods of stopping the MxC when a Stop Command is sent:

Decelerate to Stop (also referred to as, “Ramp to Stop”)

Coast to Stop

DC Injection Braking Stop

Coast to Stop (with or without a timer)

Set parameter b1-03 to indicate how the MxC should stop the motor. The MxC is unable to coast to stop or use
DC braking when operating in Flux Vector Control.

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

b1-03

Stopping Method
Selection

Selects the stopping method when the Run
Command is removed.
0: Decelerate to stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast with Timer (A new Run Command

is ignored if received before the timer
expires).

0 to 3 *

0

No

Q

Q

Q

Stopping Method

b1-05

Minimum Output
Frequency (E1-09)
or Less Operation
Selection

Operation method when frequency reference
is less than minimum output frequency set in
E1-09.
0: Operates according to frequency reference

(E1-09 is disabled).

1: Output shuts off (coast to stop if less than

E1-09).

2: Operates according to E1-09 (frequency

reference set to E1-09).

3: Zero speed (frequency reference becomes

zero when less than E1-09).

0 to 3

0

No

No

No

A

Zero-Speed Oper

b2-01

DC Injection Brak-
ing Start Fre-
quency

Sets the frequency at which DC injection
braking starts when decelerate to stop (b1-03
= 0) is selected. If b2-01< E1-09, DC Injec-
tion braking starts at E1-09.
Note: Zero Speed restrictions are active in

Flux Vector Mode.

0.0 to

10.0

0.5 Hz

No

A

A

A

DCInj Start Freq

b2-02

DC Injection Brak-
ing Current

Sets the DC injection braking current as a per-
centage of the MxC rated current.
Note: The DC excitation current is deter-

mined by the setting in E2-03 when

operating in Flux Loop Vector Control

Method.

0 to
100

50%

No

A

A

No

DCInj Current

b2-03

DC Injection Brak-
ing Time/DC Exci-
tation Time at Start Sets the time of DC injection braking at start

in units of 0.01 seconds.

0.00

to

10.00

0.00 s

No

A

A

A

DCInj Time
@Start