6

-48

‹

Detecting Motor Torque

If an excessive load is placed on the machinery (overtorque) or the load is suddenly lightened (undertorque),
an alarm signal is output to multi-function output terminal M1-M2, P1-PC, P2-PC, P3-C3, or P4-C4.

To use the overtorque/undertorque detection function, set B, 17, 18, 19 (overtorque/undertorque detection NO/
NC) in one of the following parameters: H2-01 to H2-05 (Terminals M1-M2, P1-PC, P2-PC, P3-C3, and P4-
C4 Function Selection).

The overtorque/undertorque detection level is the current level (MxC rated output current 100%) in V/f con-
trol, and the motor torque (motor rated torque 100%) in vector control.

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

L6-01

Torque Detection
Selection 1

0: Overtorque/undertorque detection dis-

abled.

1: Overtorque detection only with speed

agreement; operation continues after over-
torque (warning).

2: Overtorque detected continuously during

operation; operation continues after over-
torque (warning).

3: Overtorque detection only with speed

agreement; output stopped upon detection
(protected operation).

4: Overtorque detected continuously during

operation; output stopped upon detection
(protected operation).

5: Undertorque detection only with speed

agreement; operation continues after over-
torque (warning).

6: Undertorque detected continuously dur-

ing operation; operation continues after
overtorque (warning).

7: Undertorque detection only with speed

agreement; output stopped upon detection
(protected operation).

8: Undertorque detected continuously dur-

ing operation; output stopped upon detec-
tion (protected operation).

0 to 8

0

No

A

A

A

Torq Det 1 Sel

L6-02

Torque Detection
Level 1

Open Loop Vector Control: Motor rated
torque is set as 100%.
V/f Control: MxC rated current is set as
100%.

0 to 300

150%

No

A

A

A

Torq Det 1 Lvl

L6-03

Torque Detection
Time 1

Sets the overtorque/undertorque detection
time in 1-second units.

0.0 to

10.0

0.1 s

No

A

A

A

Torq Det 1 Time

L6-04

Torque Detection
Selection 2

Multi-function output for overtorque detec-
tion 1 is output to multi-function contact out-
put when overtorque detection 1 NO or
overtorque detection 1 NC is selected.
Multi-function output for overtorque detec-
tion 2 is output to multi-function contact out-
put when overtorque detection 2 NO or
overtorque detection 2 NC is selected.

0 to 8

0

No

A

A

A

Torq Det 2 Sel

L6-05

Torque Detection
Level 2

0 to
300

150%

No

A

A

A

Torq Det 2 Lvl

L6-06

Torque Detection
Time 2

0.0 to

10.0

0.1 s

No

A

A

A

Torq Det 2 Time