Basic settings – Yaskawa Matrix Converter User Manual

Page 87

Advertising
background image

4

-4

‹

Basic Settings

Switch to the Quick Programming Mode (“QUICK” will be displayed on the LCD screen), and then set the
following parameters. Refer to Chapter 3 Digital Operator and Modes for digital operator operating proce-
dures and to Chapter 5 Parameters and Chapter 6 Parameter Settings by Function for details on the Parame-
ters.

Parameters that must be set are listed in Table 4.1 and those that are set according to the application are listed
in Table 4.1.

Table 4.1 Parameters that Must Be Set

Parameter

Number

Name

Description

Setting

Range

Default

Page

A1-02

Control Method
Selection

Selects the Control Method.
0: V/f Control Method without a PG encoder
2: Open Loop Vector
3: Flux Vector (Closed Loop Vector)

0, 2, or 3

2

5-7

b1-01

Frequency Refer-
ence Selection

Selects the frequency reference input source.
0: Operator - Digital preset speed U1-01 or d1-

01 to d1-17.

1: Terminals - Analog input terminal A1 (or

terminal A2 based on parameter H3-09).

2: Serial Com - Modbus RS-422/485 terminals

R+, R-, S+, and S-.

3: Option PCB - Option card connected on

2CN.

0 to 3

1

5-9
6-2

6-67
6-84

b1-02

Run Source

Selects the Run Command input source.
0: Operator - RUN and STOP keys on digital

operator.

1: Terminals - Contact closure on terminals S1

or S2.

2: Serial Com - Modbus RS-422/485 terminals

R+, R-, S+, and S-.

3: Option PCB - Option card connected on

2CN.

0 to 3

1

5-9
6-8

6-67
6-84

b1-03

Stopping Method
Selection

Selects the stopping method when the Run
Command is removed.
0: Decelerate to stop
1: Coast to Stop
2: DC Injection to Stop
3: Coast with Timer (A new Run Command is

ignored if received before the timer expires).

0 to 3

*1

0

5-9

6-11

C1-01

Acceleration
Time 1

Sets the time to accelerate from zero to maxi-
mum frequency.

0.0 to 6000.0

*2

10.0 s

5-16
6-17

C1-02

Deceleration
Time 1

Sets the time to decelerate from maximum fre-
quency to zero.

0.0 to 6000.0

*2

10.0 s

5-16
6-17

C6-02

Carrier Fre-
quency Selection

Select carrier frequency
2: 4.0 kHz
4: 8.0 kHz
6: 12.0 kHz

2, 4, or 6

*3 *4

2

5-19

d1-01 to d1-

04 and d1-

17

Frequency
References 1 to 4
and Jog
Frequency
Reference

Set the required speed references for multi-step
speed operation or jogging.

0.00 to 120.00

d1-01 to

d1-04:

0.00 Hz

d1-17:

6.00 Hz

5-20
5-21