Alarm detection – Yaskawa Matrix Converter User Manual

Page 332

Advertising
background image

Protective and Diagnostic Functions

7-

11

‹

Alarm Detection

Alarms are detected as a type of MxC protection function that do not operate the fault contact output. The sys-
tem will automatically returned to its original status once the cause of the alarm has been removed.

The digital operator display flashes and the alarm is output from the multi-function outputs (H2-01 to H2-03).

When an alarm occurs, take appropriate countermeasures according to the table below.

Table 7.2 Alarm Displays and Processing

Display

Meaning

Probable causes

Corrective Actions

EF

(flashing)

External

Fault

Forward/Reverse Run Commands
Input Together
Both the Forward and Reverse Run
Commands have been on for more
than 0.5 s.

-

Check the sequence of the Forward
and Reverse Run Commands.
The motor will stop by the stopping
method that is set in b1-03 when this
fault occurs.

UV

(flashing)

PS Und-

ervolt

Control Circuit Undervoltage
The following conditions occurred
when there was no run signal.
• The control circuit voltage was

below the Undervoltage Detection
Level Setting (L2-05).

• The control power supply voltage

was below the CUV level.

See causes for UV1 and UV2 faults in
the previous table.

See corrective actions for UV1 and
UV2 faults in the previous table.

AUV

(flashing)

Power

UV

Power Supply Undervoltage
The power supply is below the under-
voltage detection level (L2-21).
200 V class: Approx. 150 VAC
400 V class: Approx. 300 VAC

• The power voltage is too high.
• The power capacity is too small.
• The power distortion is too large.

• Decrease the voltage to be within

specifications.

• Increase the power capacity.
• Decrease the impedance of the input

power wiring.

For details, refer to MxC Application
Precautions
in Chapter 10.

An open phase occurred in the input
power supply.

Check and correct the open-phase con-
dition or the imbalance of the input
power.
Clear the fault after correcting the
problem or removing its cause.

Check if a short circuit occurred
between the following terminals.
R/L1 ← → r2,
S/L2 ← → s2,
T/L3 ← → t2

Replace the MxC.

FDV

(flashing)

Freq

DEV

Power Supply Frequency Fault
The fluctuation in the power fre-
quency exceeded the allowable
amount.

• A momentary power loss occurred.
• The wiring terminals for the input

power supply are loose.

• The voltage fluctuations in the

input power supply are too large.

• The voltage balance between

phases is not equal.

• Increase the power capacity.
• Decrease the impedance of the input

power wiring.

Clear the fault after correcting the
problem or removing its cause.
For details, refer to MxC Application
Precautions
in Chapter 10.

Power Supply Undervoltage
The power supply is below the under-
voltage detection level (L2-21).
200 V class: Approx. 150 VAC
400 V class: Approx. 300 VAC

• A momentary power loss occurred.
• The wiring terminals for the input

power supply are loose.

• The voltage fluctuations in the

input power supply are too large.

• The voltage balance between

phases is not equal.

• Increase the power capacity.
• Decrease the impedance of the input

power wiring.

Clear the fault after correcting the
problem or removing its cause.
For details, refer to MxC Application
Precautions
in Chapter 10.

Advertising