b2: DC Injection Braking

b1-07

Local/Remote
Run Selection

Used to set the operation mode by switch-
ing to the Remote mode using the
LOCAL/REMOTE key.
0: Run signals that are input during

mode switching are disregarded.
(Input Run signals after switching the
mode.)

1: Run signals become effective imme-

diately after switching to the Remote
mode.

0 or 1

0

No

A

A

A

186H

-

LOC/REM RUN
Sel

b1-08

Run Command
Selection During
Program

Used to set an operation interlock in pro-
gramming modes.
0: Cannot operate.
1: Can operate (Disabled when digital

operator is set to select Run Com-
mand (when b1-02 = 0)).

2

*2

:The MENU key is disabled during

run.

0 or 2

*2

0

No

A

A

A

187H

-

RUN CMD at
PRG

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

b2-01

DC Injection
Braking Start Fre-
quency

Sets the frequency at which DC injection
braking starts when decelerate to stop
(b1-03 = 0) is selected. If b2-01< E1-09,
DC Injection braking starts at E1-09.
Note: Zero Speed restrictions are active

in Flux Vector Mode.

0.0 to

10.0

0.5 Hz

No

A

A

A

189H

6-11

6-123

DCInj Start Freq

b2-02

DC Injection
Braking Current

Sets the DC injection braking current as a
percentage of the MxC rated current.
Note: The DC excitation current is deter-

mined by the setting in E2-03 when

operating in Flux Loop Vector

Control Method.

0 to
100

50%

No

A

A

No

18AH

6-11
6-15

DCInj Current

b2-03

DC Injection
Braking Time/DC
Excitation Time at
Start

Sets the time of DC injection braking at
start in units of 0.01 seconds.

0.00

to

10.00

0.00 s

No

A

A

A

18BH

6-11
6-15

DCInj Time
@Start

b2-04

DC Injection
Braking Time at
Stop

Sets the time length of DC injection brak-
ing at stop in units of 0.01 seconds.
1: When b1-03 = 2, actual DC Injection

time is calculated as follows: (b2-04)
× 10 × (OutputFreq) / (E1-04)

2: When b1-03 = 0, this parameter deter-

mines the amount of time DC Injec-
tion is applied to the motor at the end
of the decel ramp.

3: This should be set to a minimum of

0.50 seconds when using HSB. This
will activate DC injection during the
final portion of HSB and help ensure
that the motor stops completely.

0.00

to

10.00

0.50 s

No

A

A

A

18CH

6-12

DCInj Time
@Stop

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector