Wiring Control Circuit Terminals

2-

19

‹

Control Circuit Terminal Functions

The functions available by using the control circuit terminals are shown in Table 2.8. Use the appropriate ter-
minals for the correct purposes.

Table 2.8 Control Circuit Terminals

Type

No.

Signal Name

Function

Signal Level

Se-

quence

input

signals

S1

Forward Run/Stop Command Forward run when on, stopped when off.

24 VDC, 8 mA
Photocoupler isolation

S2

Reverse Run/Stop Command Reverse run when on, stopped when off.

S3

Multi-Function Input 1

*1

Default: External Fault when on.

S4

Multi-Function Input 2

*1

Default: Fault Reset when on.

S5

Multi-Function Input 3

*1

Default: Multi-Speed Reference 1 enabled
when on.

S6

Multi-Function Input 4

*1

Default: Multi-Speed Reference 2 enabled
when on.

S7

Multi-Function Input 5

*1

Default: Jog Frequency selected when on.

S8

Multi-Function Input 6

*1

Default: External Baseblock when on.

S9

Multi-Function Input 7

*1

Default: Multi-Speed Reference 3 enabled
when on.

S10

Multi-Function Input 8

*1

Default: Multi-Speed Reference 4 enabled
when on.

S11

Multi-Function Input 9

*1

Default: Accel/Decel Time selected when on.

S12

Multi-Function Input 10

*1

Default: Emergency Stop (N.O. contact)
when on.

SC

Sequence input common

-

Analog

input

signals

+V

+15 V power output

+15 V power supply for analog references

+15 V
(Max current: 20 mA)

-V

-15 V power output

-15 V power supply for analog references

-15 V
(Max current: 20 mA)

A1

Master Speed Frequency
Reference

-10 to +10 V/-100 to 100%
0 to +10 V/100%

-10 to +10 V, 0 to +10 V
(Input impedance:
20 k

Ω)

A2

Multi-Function Analog Input

4 to 20 mA/100%, -10 to +10 V/-100 to
+100%, 0 to +10 V/100%
Default: Added to terminal A1
(H3-09 = 0)

4 to 20 mA (Input imped-
ance: 250

Ω)

-10 to +10 V, 0 to +10 V
(Input impedance:
20 k

Ω)

A3

Multi-Function Analog Input

-10 to +10 V/-100 to +100%, 0 to +10 V/
100%
Default: Analog speed 2 (H3-05 = 2)

-10 to +10 V, 0 to +10 V
(Input impedance:
20 k

Ω)

AC

Analog reference common

0 V

-

E(G)

Shield wire, optional ground
line connection point

-

-