Machine Protection

6-

49

Multi-function Digital Outputs (H2-01 to H2-05)

„

L6-01 and L6-04 Set Values and LCD Indicator Lights

The relationship between alarms displayed by the digital operator when overtorque or undertorque is detected
and the set values in L6-01 and L6-04 is shown in the following table.

„

Setting Example

The following diagram shows the time chart for overtorque and undertorque detection.

Overtorque Detection

Set

Value

Function

Control Methods

V/f

Open

Loop

Vector

Flux

Vector

B

Overtorque/undertorque detection 1 N.O. (N.O. contact: Overtorque/undertorque detection when on)

Yes

Yes

Yes

17

Overtorque/undertorque detection 1 N.C. (N.C. Contact: Overtorque/undertorque detection when off)

Yes

Yes

Yes

18

Overtorque/undertorque detection 2 N.O. (N.O. Contact: Overtorque/undertorque detection when on)

Yes

Yes

Yes

19

Overtorque/undertorque detection 2 N.C. (N.C. Contact: Overtorque/undertorque detection when off)

Yes

Yes

Yes

Set

Value

Function

LCD Indications

Overtorque/

Undertorque

Detection 1

Overtorque/

Undertorque

Detection 2

0

Overtorque/undertorque detection disabled.

-

-

1

Overtorque detection only with speed matching: Operation continues after
overtorque (warning).

OL3 flashes

OL4 flashes

2

Overtorque detected continuously during run: Operation continues after
overtorque (warning).

OL3 flashes

OL4 flashes

3

Overtorque detection only with speed matching: Output stopped upon detec-
tion (protected operation).

OL3 lit

OL4 lit

4

Overtorque detected continuously during run: Output stopped upon detec-
tion (protected operation).

OL3 lit

OL4 lit

5

Undertorque detection only with speed matching: Operation continues after
overtorque (warning).

UL3 flashes

UL4 flashes

6

Undertorque detected continuously during run: Operation continues after
overtorque (warning).

UL3 flashes

UL4 flashes

7

Undertorque detection only with speed matching: Output stopped upon
detection (protected operation).

UL3 lit

UL4 lit

8

Undertorque detected continuously during run: Output stopped upon detec-
tion (protected operation).

UL3 lit

UL4 lit

*

*

L6-02 or L6-05

L6-03 or
L6-06

L6-03 or
L6-06

Overtorque detection 1 NO
or overtorque detection 2 NO

on

on

*

Overtorque detection disabled bandwidth is approximately 10% of the MxC rated output

current (or motor rated torque).

Motor current (output torque)