Yaskawa Matrix Converter User Manual

Page 198

Advertising
background image

Improved Operating Efficiency

6-

33

„

Adjusting Slip Compensation Gain

Switch the C3-01 parameter settings as shown below by changing the control method.

V/f Control: 0.0

Open Loop Vector Control: 1.0

Flux Vector Control: 1.0

Set C3-01 to 1.0 to compensate the rated slip set using the rated torque output status.

Adjust the slip compensation gain using the following procedure.

1. Set E2-02 (Motor Rated Slip) and E2-03 (Motor No-Load Current) correctly.

Use the following formula to calculate the motor rated slip from the values on the motor nameplate.
amount of motor rated slip (Hz) =

motor rated frequency (Hz) - no. of rated rotations (min

−1

)

× no. of motor poles / 120

Set the values for rated voltage, rated frequency, and no-load current in the motor unladen current. The
motor rated slip is set automatically in the vector control using Auto-Tuning.

2. In V/f control, set C3-01 to 1.0. Setting this parameter to 0.0 disables slip compensation.
3. Apply a load, and measure the speed to adjust the slip compensation gain. Adjust the slip compensation

gain by 0.1 at a time. If the speed is less than the target value, increase the slip compensation gain, and if
the speed is greater than the target value, reduce the slip compensation gain.

For Flux Vector Control, the slip compensation gain is used as the motor temperature compensation gain.
When the motor temperature increases, the motor’s internal parameter increases, resulting in an increase in
slip. If C3-01 is set, the amount of slip is adjusted as the temperature rises. Set C3-01 if the amount of torque
varies with the temperature when using torque control or a torque limit. The larger the value of C3-01, the
larger the compensation.

„

Adjusting Slip Compensation Primary Delay Time Constant

Set the slip compensation primary delay time constant in ms.

Switch the default settings as follows by changing the control method.

V/f Control: 2000 ms

Open Loop Vector Control: 200 ms

Normally, there is no need to change these settings from their original values. Lower the set value only when
the slip compensation response is low. When the speed is unstable, increase the set value.

„

Adjusting Slip Compensation Limit

Set the upper limit for the slip compensation amount as a percent, taking the motor rated slip amount as 100%.

If the speed is lower than the target value but does not change even after adjusting the slip compensation gain,
the motor may have reached the slip compensation limit. Increase the limit, and check the speed again. Make
sure that the value of the slip compensation limit and reference frequency does not exceed what the applica-
tion can handle.

The following diagram shows the slip compensation limit for the constant torque range and fixed output range.

Advertising