Dc braking stop, Coast to stop with timer, Info – Yaskawa Matrix Converter User Manual

Page 179

Advertising
background image

6

-14

„

DC Braking Stop

If the Stop Command is input (i.e., the Run Command is turned off) when b1-03 is set to 2, then the MxC will
wait for the duration set to L2-03 (Momentary Power Loss Minimum Baseblock Time) before applying DC
Injection Braking current (set in b2-02) to the motor. DC Injection Brake time is determined by the set value in
b2-04 and the output frequency.

Fig 6.15 DC Injection Braking (DB) Stop

„

Coast to Stop with Timer

If the Stop Command is input (i.e., the Run Command is turned off) when b1-03 is set to 3, the MxC output
will be shut off to allow the motor to coast to stop. After the Stop Command is input, Run Commands are
ignored until time T has elapsed. The length of T depends upon the output frequency when the Stop Command
is input as well as the deceleration time.

Fig 6.16 Coast to Stop with Timer

INFO

After the Stop Command is input, Run Commands are ignored until the Minimum Baseblock Time (L2-03) has
elapsed.

INFO

Lengthen the Momentary Power Loss Minimum Base Block Time (L2-03) when overcurrent (OC) occurs while
stopping.

MxC output voltage interrupted

Output frequency

Run Command

on

off

Minimum Base Block

Time (L2-03)

DC injection brake time

DC injection brake

10

100% (maximum output frequency)

Output frequency at
Stop Command input

DC injection brake time

b2-04

× 10

b2-04

Output

frequency

Run Command

on

on

on

off

off

MxC output voltage interrupted

Operation wait time T

100% (Maximum output frequency)

Minimum output frequency

Output frequency at
Stop Command input

Operation wait time T

Deceleration time
(e.g., C1-02)

Minimum Base Block

Time (L2-03)

Advertising