L4: reference detection – Yaskawa Matrix Converter User Manual

Page 146

Advertising
background image

5

-46

* Not available for the MxC models CIMR-ACA4110 and 4160 for V/f Control.

„

L4: Reference Detection

L3-06

Stall Prevention
Level During Run

This parameter is enabled when L3-05 is
set to “1” or “2”. MxC rated current is set
as 100%.
Decrease the set value if stalling or exces-
sive current occurs with the defaults.

30 to

200

160%

No

A

No

No

494H

4-17
6-43

StallP Run Level

L3-14

Stall prevention
level during decel

Enabled if L3-04 is set to 1.
Set the level as a percentage of the MxC
rated current.
Usually setting is not necessary. Lower
the value if the motor stalls at the default.

100 to

200

150%

No

A

A

A

4E9H

6-23

StallP Decel Lvl

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

L4-01

Speed Agreement
Detection Level

Effective when “Desired frequency
(speed) agree 1,” “Frequency (FOUT)
detection 1,” or “Frequency (FOUT)
detection 2” is set for a multi-function
output.
Frequencies to be detected are set in Hz
units.

0.0 to
120.0

0.0 Hz

No

A

A

A

499H

6-44

Spd Agree Level

L4-02

Speed Agreement
Detection Width

Effective when “Frequency (speed) agree
1,” “Frequency (FOUT) agree 1,” or
“Frequency (FOUT) detection 2” is set
for a multi-function output.
Sets the frequency detection width in Hz
units.

0.0 to

20.0

2.0 Hz

No

A

A

A

49AH

6-44

Spd Agree Width

L4-03

Speed Agreement
Detection
Level(+/-)

Effective when “Desired frequency
(speed) agree 2,” “Frequency (FOUT)
detection 3,” or “Frequency (FOUT)
detection 4” is set for a multi-function
output.
Frequency that should be detected is set
in Hz units.

-120.0

to

+120.0

0.0 Hz

No

A

A

A

49BH

6-44

Spd Agree Lvl +-

L4-04

Speed Agreement
Detection Width
(+/-)

Effective when “Frequency (speed) agree
2,” “Frequency (FOUT) detection 3,” or
“Frequency detection 4” is set for a multi-
function output.
Frequency detection width is set in Hz
units.

0.0 to

20.0

2.0 Hz

No

A

A

A

49CH

6-44

Spd Agree Wdth
+-

L4-05

Frequency Refer-
ence Loss Detec-
tion Selection

0: Stop (Operation follows the frequency

reference.)

1: Operation at 80% speed continues.

(At 80% of speed before the fre-
quency reference was lost)

Frequency reference is lost: Frequency
reference dropped over 90% in 400 ms.

0 or 1

0

No

A

A

A

49DH

6-64

Ref Loss Sel

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector