Speed limit (frequency reference limit function), Limiting maximum output frequency, Limiting minimum frequency – Yaskawa Matrix Converter User Manual

Page 195: Speed limit (frequency reference limit func- tion), Related parameters

Advertising
background image

6

-30

Speed Limit (Frequency Reference Limit Func-
tion)

This section explains how to limit the motor speed.

‹

Limiting Maximum Output Frequency

Use parameter d2-01 to set the maximum speed of the motor.

Set the upper limit value of the MxC output frequency as a percent, taking E1-04 (Maximum Output Fre-
quency) to be 100%.

„

Related Parameters

‹

Limiting Minimum Frequency

Use parameters d2-02 or d2-03 not to rotate the motor at a given frequency or less.

There are two ways to set the minimum frequency:

Adjust the minimum level for all frequencies.

Adjust the minimum level for the master speed frequency (i.e., the lower levels of the jog frequency, multi-
step speed frequency, and auxiliary frequency will not be adjusted).

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

d2-01

Frequency Refer-
ence Upper Limit

Set the output frequency upper limit as a per-
cent, taking the max. output frequency to be
100%.

0.0 to

110.0

100.0%

No

A

A

A

Ref Upper Limit

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

d2-02

Frequency Refer-
ence Lower Limit

Sets the output frequency lower limit as a per-
centage of the maximum output frequency.

0.0 to

110.0

0.0%

No

A

A

A

Ref Lower Limit

d2-03

Master Speed Ref-
erence Lower
Limit

Set the master speed reference lower limit as a
percent, taking the max. output frequency to
be 100%.

0.0 to

110.0

0.0%

No

A

A

A

Ref1 Lower Limit