* The FM output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify Mode while the motor is stopped.

The AM output can be adjusted when the H4-05 or H4-06 setting is displayed in Quick, Advanced, or Verify Mode while the motor is stopped.

For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

H4-01

Terminal FM
Monitor Selection

Sets the number of the monitor item to be
output (U1-††) from terminal FM.
Items that can be set differ in accordance
with the selected control modes.
For information on the parameters for
which analog output is possible, refer to
U: Monitors.

1 to 99

2

No

A

A

A

41DH

6-79

Terminal FM Sel

H4-02

Terminal FM
Gain Setting

Sets the multi-function analog output 1
voltage level gain.
Sets whether the monitor item output will
be output in multiples of 10 V.
The maximum output from the terminal is
10 V.
A meter calibration function is available.

*

0.00 to

2.50

1.00

Yes

Q

Q

Q

41EH

4-5

6-79

Terminal FM
Gain

H4-03

Terminal FM Bias
Setting

Sets the multi-function analog output 1
voltage level bias.
Sets output characteristic up/down paral-
lel movement as a percentage of 10 V.
The maximum output from the terminal is
10 V.
A meter calibration function is available.

*

-10.0 to

+10.0

0.0%

Yes

A

A

A

41FH

6-79

Terminal FM Bias

H4-04

Terminal AM
Monitor Selection

Sets the number of the monitor item to be
output (U1-††) from terminal AM.
Items that can be set differ in accordance
with the selected control modes.
For information on the parameters for
which analog output is possible, refer to
U: Monitors.

1 to 99

3

No

A

A

A

420H

6-79

Terminal AM Sel

H4-05

Terminal AM
Gain Setting

Set the voltage level gain for multi-func-
tion analog output 2.
Set the number of multiples of 10 V to be
output as the 100% output for the monitor
items. The maximum output from the ter-
minal is 10 V.
A meter calibration function is available.

*

0.00 to

2.50

0.50

Yes

Q

Q

Q

421H

4-5

6-79

Terminal AM
Gain

H4-06

Terminal AM
Bias Setting

Sets the multi-function analog output 2
voltage level bias.
Sets output characteristic up/down paral-
lel movement as a percentage of 10 V.
The maximum output from the terminal is
10 V.
A meter calibration function is available.

*

-10.0 to

+10.0

0.0%

Yes

A

A

A

422H

6-79

Terminal AM
Bias

H4-07

Terminal FM Sig-
nal Level Selec-
tion

Sets the signal output level for multi-
function output 1 (terminal FM)
0: -10 to 10 VDC output
1: -10 to 10 VDC output

0 or 1

0

No

A

A

A

423H

6-79

AO Level Select 1

H4-08

Terminal AM Sig-
nal Level Selec-
tion

Sets the signal output level for multi-
function output 2 (terminal AM)
0: 0 to +10 VDC output
1: 0 to

±10 VDC output

0 or 1

0

No

A

A

A

424H

-

AO Level Select 2