H5: MEMOBUS Communications

* Set H5-01 to 0 to disable MxC responses to MEMOBUS communications.

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

H5-01

MxC Node
Address

Set the MxC's station address.

0 to 20

*

1F

No

A

A

A

425H

6-84

Serial Comm Adr

H5-02

Communication
Speed Selection

Set the baud rate for MEMOBUS com-
munications of communications connec-
tion terminals.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps

0 to 4

3

No

A

A

A

426H

6-84

Serial Baud Rate

H5-03

Communication
Parity Selection

Set the parity for MEMOBUS communi-
cations of CN6.
0: No parity
1: Even parity
2: Odd parity

0 to 2

0

No

A

A

A

427H

6-84

Serial Com Sel

H5-04

Stopping Method
After Communi-
cation Error

Set the stopping method for communica-
tions errors.
0: Deceleration to stop
1: Coast to stop
2: Emergency stop
3: Continue operation

0 to 3

3

No

A

A

A

428H

6-84

Serial Fault Sel

H5-05

Communication
Fault Detection
Selection

Set whether or not a communications tim-
eout is to be detected as a communica-
tions error.
0: Do not detect.
1: Detect

0 or 1

1

No

A

A

A

429H

6-84

Serial Flt Dtct

H5-06

MxC Transmit
Wait Time

Set the time from the MxC receiving data
to when the MxC starts to send.

5 to 65

5 ms

No

A

A

A

42AH

6-84

Transmit Wait-
TIM

H5-07

RTS Control
Selection

Select to enable or disable RTS control.
0: Disabled (RTS is always on)
1: Enabled (RTS turns on only when

sending)

0 or 1

1

No

A

A

A

42BH

6-84

RTS Control Sel

H5-10

Unit Selection for
Memobus Regis-
ter 0025H

Selects the units used for MEMOBUS
registry 0025H (monitors the output volt-
age reference).
0: 0.1 V units
1: 1 V units

0 or 1

0

No

A

A

A

436H

6-84

MEMOBUS 25H
UNIT