Parameter Tables

5-

43

‹

L: Protection Function

The following settings are made with the protection function parameters (L parameters): Motor selection func-
tion, power loss ridethrough function, stall prevention function, frequency detection, torque limits, and hard-
ware protection.

„

L1: Motor Overload

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

L1-01

Motor Overload
Protection Selec-
tion

Sets the motor thermal overload protec-
tion (OL1) based on the cooling capacity
of the motor.
0: Disabled.
1: Standard Fan Cooled (< 10:1 motor)
2: Standard Blower Cooled (10:1 motor)
3: Vector Motor (

≤1000:1 motor)

0 to 3

1

No

Q

Q

Q

480H

4-5

6-51

MOL Fault Select

L1-02

Motor Overload
Protection Time

Sets the motor thermal overload protec-
tion (OL1) time. A larger L1-02 time will
increase the time before an OL1 fault will
occur.

0.1 to

5.0

1.0

min

No

A

A

A

481H

6-51

MOL Time Const

L1-03

Motor Overheat
Alarm Operation
Selection

Sets operation selection when the motor
temperature analog input (H3-09 = E)
exceeds the OH3 alarm level (1.17V)
0: Decelerate to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

0 to 3

3

No

A

A

A

482H

6-54

Mtr OH Alarm
Sel

L1-04

Motor Overheat
Fault Operation
Selection

Sets stopping method when the motor
temperature analog input
(H3-09 = E) exceeds the OH4 fault level.
0: Decelerate to Stop
1: Coast to Stop
2: Fast-Stop

0 to 2

1

No

A

A

A

483H

6-54

Mtr OH Fault Sel

L1-05

Motor Tempera-
ture Input Filter
Time

This parameter adjusts the filter on the
motor temperature analog input (H3-09 =
E). Increase to add stability, decrease to
improve response.

0.00 to

10.00

0.20 s

No

A

A

A

484H

6-54

Mtr Temp Filter