Stall Prevention during Run

Stall Prevention during Run prevents the motor from stalling by automatically lowering the MxC's output fre-
quency when a transient overload occurs while the motor is operating at a constant speed.

Stall Prevention during Run is enabled only during V/f Control. If the MxC output current continues to exceed
the setting in parameter L3-06 for 100 ms or longer, the motor speed is reduced. Set whether to enable or dis-
able deceleration time using parameter L3-05. Set the deceleration time using C1-02 (Deceleration Time 1) or
C1-04 (Deceleration Time 2).

If the MxC output current reaches the set value in L3-06 - 2% (MxC Rated Output Current), the motor will
accelerate again at the frequency set or the acceleration time set.

„

Related Parameters

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control Methods

Display

V/f

Open

Loop

Vector

Flux

Vector

L3-05

Stall Prevention
Selection During
Running

Selects the stall prevention method to use to
prevent MxC faults during run.
0: Disabled.- MxC runs a set frequency. A

heavy load may cause the MxC to trip on
an OC or OL fault.

1: Decel Time 1 - In order to avoid stalling

during heavy loading, the MxC will decel-
erate at Decel time 1 (C1-02) if the output
current exceeds the level set by L3-06.
Once the current level drops below the
L3-06 level, the MxC will accelerate back
to its frequency reference at the active
acceleration rate.

2: Decel Time 2 - Same as setting 1 except

the MxC decelerates at Decel Time 2 (C1-
04).
When output frequency is 6 Hz or less,
Stall Prevention during Run is disabled
regardless of the setting in L3-05.

0 to 2

1

No

A

No

No

StallP Run Sel

L3-06

Stall Prevention
Level During Run-
ning

This parameter is enabled when L3-05 is set
to “1” or “2”. MxC rated current is set as
100%.
Decrease the set value if stalling or excessive
current occurs with the defaults.

30 to

200

160%

No

A

No

No

StallP Run Level