Parameter Tables

5-

17

* The setting range for accel/decel times depends on the setting of C1-10 (Accel/Decel Time Setting Units). If C1-10 is set to 0, the setting range is 0.00 to 600.00 (s).

„

C2: S-Curve Acceleration/Deceleration

„

C3: Motor Slip Compensation

C1-11

Accel/Decel
Switch Frequency

Sets the frequency for automatic switch-
ing of accel/decel times.
Fout < C1-11: Accel/Decel Time 4
Fout

≥C1-11: Accel/Decel Time 1

Multi-function inputs “Multi-Acc/Dec 1”
and “Multi-Acc/Dec 2” have priority over
C1-11.
Note: With Multi-Function Input, Accel/

Decel Time 1 and 2 will take prece-

dence.

0.0 to
120.0

0.0 Hz

No

A

A

A

20AH

4-17
6-17

Acc/Dec SW Freq

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

C2-01

S-Curve Charac-
teristic at Accel
Start

All sections of the S-curve characteristic
time are set in seconds units.
When the S-curve characteristic time is
set, the accel/decel times will increase by
only half of the S-curve characteristic
times at start and end.

0.00 to

2.50

0.20 s

No

A

A

A

20BH

4-17
6-18

SCrv Acc @ Start

C2-02

S-Curve Charac-
teristic at Accel
End

0.00 to

2.50

0.20 s

No

A

A

A

20CH

4-17
6-18

SCrv Acc @ End

C2-03

S-Curve Charac-
teristic at Decel
Start

0.00 to

2.50

0.20 s

No

A

A

A

20DH

4-17
6-18

SCrv Dec @ Start

C2-04

S-Curve Charac-
teristic at Decel
End

0.00 to

2.50

0.00 s

No

A

A

A

20EH

4-17
6-18

SCrv Dec @ End

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

C3-01

Slip Compensa-
tion Gain

This parameter is used to increase motor
speed to account for motor slip by boost-
ing the output frequency. If the speed is
lower than the frequency reference,
increase C3-01. If the speed is higher
than the frequency reference, decrease
C3-01.
Note: Adjustment is not normally

required. When operating in Open

Loop Vector, this parameter works

as a function to set the proper

amount of gain.

0.0 to

2.5

1.0

*

Yes

A

A

A

20FH

4-15
6-32

Slip Comp Gain

Parameter

Number

Name

Description

Setting

Range

Default

Change

during

Run

Control

Methods

MEMO-

BUS

Register

Page

Display

V/f

Open

Loop

Vector

Flux

Vector

Run Command

Output frequency

Time

on

off

C2-02

C2-03

C2-04

C2-01